
17. Appendix H
17.1. Important Functional Considerations
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
537
July 2010
Honeywell
Function Indication
Consideration
Incoming Analog
value with status from
fieldbus device to
Experion function
block
A BAD status from
fieldbus device does
not
force Experion function
block value to NaN.
F
OUNDATION
Fieldbus devices may
show the last good value when the
current value is indicated as BAD via
the status. This is
Not
consistent with
normal Experion system operation.
Summary of Contents for Experion PKS Series A
Page 242: ......
Page 559: ......
Page 560: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...