17. Appendix H
17.1 Important Functional Considerations
The following tables lists some functional considerations to keep in mind when
integrating fieldbus with an Experion system.
General
Function Indication
Consideration
Fieldbus device with
previous address
assignment is added
to a Link. .
Potential to lose Link
Schedule, if FIM fails
before "uncommissioned"
device is "commissioned".
Always
remove
the address from a
used fieldbus device before you store
it.
Adding Link Master
capable device to
operating Link.
Potential for LM capable
device to assume LAS role
using empty or incorrect
Link Schedule.
See the
Guidelines for adding fieldbus
device to "live"/operating Link
in the
Maintenance, Checkout, and
Calibration
section of this document.
Link Slot Time setting
is
8
or less.
A new uncommissioned
device may not appear in
the Link directory in the
Monitoring tab.
Change the default Slot Time setting to
10
on the Link Block Parameters form
in Control Builder.
(If an uncommissioned device does not
appear, try increasing the Slot Time
value by one and cycling power to the
FIM. Repeat this action, as required.)
Using automatic
inactivate/activate
function in Load
Dialog box in Control
Builder
A component is
automatically inactivated
during the load and then
returned to its active state.
Do
not
use this automatic
inactivate/activate function, if your
process can
not
tolerate the load
disruption and consequent delay in
activation.
Fieldbus device
designated as
"backup" Link Master
can
not
handle the
Link Schedule. (Also,
see the next row.)
Device icon turns yellow
(LM without schedule) or
red (bad communications).
The FIM is the primary Link Master for
both Links. If you designate a device
as a "backup" Link Master, be sure it
has the capacity to handle the Link
Schedule. Otherwise, you may have to
reconfigure the device as a
Basic
type
and restart it to initiate the change, if
the Link Schedule is too large for it to
handle.