10. Appendix A
10.2. Standard Function Blocks
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
393
July 2010
Honeywell
Equation Options
In Automatic mode: OUT = (IN_1 + SP) x GAIN
If IN_1 has Non-Cascade status: BKCAL_OUT =
(BKCAL_IN / GAIN) - IN_1
If IN_1 has Cascade status: BKCAL_OUT =
(BKCAL_IN / GAIN) - SP
Parameters
ALERT_KEY
BAL_TIME
BKCAL_IN
BKCAL_OUT
BLOCK_ALM
BLOCK_ERR
BLOCK_ERR.DISABLED
CAS_IN
CONTROL_OPTS
GAIN
GRANT_DENY
IN_1
MODE_BLK
OUT
OUT_HI_LIM
OUT_LO_LIM
OUT_SCALE
RCAS_IN
RCAS_OUT
SHED_OPT
SP
SP_HI_LIM
SP_LO_LIM
SP_RATE_DN
SP_RATE_UP
ST_REV
STATUS_OPTS
STRATEGY
TAG_DESC
TRK_IN_D
TRK_SCALE
TRK_VAL
UPDATE_EVT
Reference
Refer to
Standard Function Block Parameters
in
Appendix
B
for definitions of each parameter.