5. Configuration
5.8. Configuring non-cache parameters
238
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Scenario
Behavior of Block Offnet Alarm
Behavior of Device Offnet System
Alarm
the device goes off
the network.)
Disabling the
reporting of the Block
Offnet Diagnostic
Alarm for an
individual FF function
block when the
device is online.
A change event is logged in the
Event Summary indicating
OFFNETALM_ENABLED is set to
OFF.
Disabling the
reporting of the Block
Offnet Diagnostic
Alarm for an
individual FF function
block when the
device is off the
network.
The previously reported Block
Offnet Alarm for that function
block changes from “Active” to
“Disabled” in the Alarm Summary.
A change event is logged in the
Event Summary indicating
OFFNETALM_ENABLED is set to
OFF.
There is no change to the Device
Offnet System Alarm.
5.8 Configuring
non-cache parameters
To configure non-cache parameters, perform the following steps.
WARNING
The non-cache capability bypasses the normal data-acquisition optimizations
which are implemented by FIM. Configuring or monitoring the non-cache
parameters can lead to performance degradation or visible anomalies
Therefore, you must configure non-cache parameters under special
circumstances recommended by Honeywell, Inc. or device vendors.
Step Action
1
On the Project mode, right-click the device instance to select
Module
Properties
.
The configuration form appears.