11. Appendix B
11.1. Standard Function Block Parameters
422
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
BKCAL_HYS
Classification
Simple Variable
Description
Defines the amount of change an output value must attain
from the limit before the limit status is turned OFF.
FF Data Type
Float
Range
0 to 50 percent of output span
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is 0.5 percent
BKCAL_IN
Classification
Record
Description
The value and status from a lower block's BKCAL_OUT
that is used to prevent reset windup and to initialize the
control loop.
FF Data Type
DS-65
Range
Usage
I/Back-Calculation Input
Length
5
Valid Views
VIEW_3
Storage
Non-Volatile
Remarks
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value