5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
188
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Step Action
Result
12
Key in >15<. Press <Tab>.
Moves cursor to Priority field and
highlights it.
13
Click
button to open dropdown menu
and select URGENT. Press <Tab>.
Moves cursor to Severity field and
highlights it.
14
Key in >15<. Press <Tab>.
Moves cursor to next field. Double click
PV High High field to highlight it.
15
Key in >85<. Press <Tab>.
Moves cursor to Priority field and
highlights it.
16
Click
button to open dropdown menu
and select URGENT. Press <Tab>.
Moves cursor to Severity field and
highlights it.
ATTENTION
For this example, we will accept the default values for the other parameters on the
Alarms tab. These values are okay for the sample loop. Please feel free to practice
entering data in the other fields, using the online Help for support.