3. Fieldbus Integration With Experion System
3.6. Notification Scheme
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
71
July 2010
Honeywell
The FIM constantly monitors the live list for each fieldbus link connected to it. When the
LAS for the link recognizes a new device at a default address, it adds it to its live list
according to the data link layer procedures. The FIM detects the change in the live list
and makes a connection to the new uncommissioned device. It gathers the following
information from the device to be passed to Control Builder.
Name Description
Data
Type
Access
PdTag
Physical Device Tag
32-byte string
Read/Write
Address Device
Address
Unsigned8 Read/Write
DevID
Globally unique Device Identifier
32-byte string
Read Only
Vendor
Vendor name string
32-byte string
Read Only
ModelName
Model Name string
32-byte string
Read Only
Rev
Application Revision
32-byte string
Read Only
ManufID
Manufacturer Identifier
Unsigned32
Read Only
DevType
Device Type code
Unsigned16
Read Only
DevRev Device
Revision Unsigned8
Read
Only
DdRev
DD Revision
Unsigned8
Read Only
Control Builder uses the device information to create an item in its Monitoring tree to
represent the new uncommissioned device on the given link. Users can now view and
configure pertinent information for the uncommissioned device through appropriate Link
block and device block configuration forms in Control Builder.
TIP
The FIM must be configured and loaded through Control Builder before you
can view it and its links through the Monitoring tab of Control Builder.
3.6 Notification
Scheme
Fieldbus versus Experion Alarm Priorities
The fieldbus alarms will be closely integrated with the existing Experion notification
system. The Experion Server will handle FIM alarms in the same way it handles Control