5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
151
July 2010
Honeywell
Step Action
Result
2
Key in >LX102< for this example or key
in a desired name consisting of up to 16
characters. Click OK.
Closes form and creates device instance
with given name in Project tab. The
illustration below is for example purposes
only.
(Note that the symbol simply indicates
that the component has not been loaded
to the controller.)
ATTENTION
Devices created in Project tab automatically include only their fixed, transducer, and
resource function blocks. If the device block type includes instantiable blocks, you
must drag and drop the instantiable block from the device type in library to the device
icon in the Project tab to instantiate (create) it in the device in Project. See
Instantiable block implementation considerations for reference.
3
Repeat this procedure to add other
devices or go to the next procedure
Assigning a device to a Link in Project.
Assigning a device to a Link in Project
Use the following procedure to assign a device to a Link associated with the applicable
FIM in the Project tab.