5. Configuration
5.5. Loading Components Online
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
215
July 2010
Honeywell
Step Action
Result
TIP
You can change the Tag and/or Address assignments for the listed devices in either
the Uncommissioned Device or the Project Device. Just double-click the entry field you
want to change to highlight it, key in the desired tag name or address assignment in
decimal, and press <Enter>. If you are changing data in an Uncommissioned Device, it
may take several minutes for the operation to complete.
The preferred address range for fieldbus devices is 20 to 40 decimal (14 to 28
hexadecimal). This provides the most optimized default network range where the first
unused node address (FUN) is 41 decimal (29 hexadecimal) and the number of
unused addresses is (NUN) is 206. We recommend that the fieldbus device
designated as the backup Link Master be given 21 decimal (15 hexadecimal) as its
assigned address. All address number entries and displays are based on the decimal
system in Control Builder, but the Fieldbus Foundation uses the hexadecimal system.
7
For matching devices, click the checkbox
for the Uncommissioned Device and
then, click the checkbox for the matching
Project Device.
Activates the
Match from
Uncommissioned Device to Project
Device
and
Match from Project Device
to Uncommissioned Device
buttons.
The following illustration is for example
purposes only.