Current output
■
Voltage output
HANDLING PRECAUTIONS
The voltage output is a constant current circuit inside. The SSR used is set to an
optimum voltage to meet the requirements of hte load. Enter the value in the
setup data. A normal SSR voltage has been set at the factory before shipment.
■
Open collector output
HANDLING PRECAUTIONS
• Do not short-circuit the positive (+) terminal of the external power supply to
terminal (43) on the DCP551. Doing so causes the open collector outputs to
malfunction. (There is no short circuit preventing circuit inside.)
• When connecting a semiconductor load such as a programmable controller
(sequencer), select a module in which the current directions match.
Use one made inoperative by the leakage current produced when the digital
outputs are shut off.
!! ""
C95
43
+ -
Load
44
4 to 20mA DC
Load resistance less than 6009
+
-
Be sure to turn off the power supply when you are installing or
removing the controller. Failure to heed this warning may lead to
electric shock.
Chapter 4. WIRING
4-7 Control Output Connection
4-9
WARNING