12-2 Calibration Procedures
12-7
Chapter 12. CALIBRATION
■
Enter calibration mode
(1) Release keylock. (
PARA
PA01=0
)
(2) Press
DISP key
to permit ordinary indication condition.
Change to READY (
RUN
and
HLD
are off) and AUTO (
MAN
off) modes.
The following LEDs will illuminate after the above operations.
RUN
LED is OFF
HLD
LED is OFF
MAN
LED is OFF
Figure 12-2.
(3) To enter calibration mode, hold down the
FUNC key
, and press
SETUP key
and
ENTER key
simultaneously.
The display will show the symbols described in Figure 12-3. If the indication is dif-
ferent, repeat the above procedure after pushing
DISP key
to refresh the display.
(4) To select individual calibration items, press
↑
,
↓
,
←
, or
→
keys
to select the item
by scrolling, then
SETUP key
, and
ENTER key
.
The order of calibration items is described in Table 12-2.