Chapter 7. PARAMETER SETUP
From
C11
to
C20
“-----” is displayed and setting cannot be performed on model with one PV input channel.
0 to 16
: t/c
48 to 52 : linear (DC current, DC voltage)
64 to 71 : RTD
96 to 103: RTD
128 to 134: linear (DC current, DC voltage)
[Description:]
For details see range numbers listed in ÒSection 2-3
Input Type and Range NumberÓ (page 2-8).
0
C 11
11
PV2 range number
0: ûC Celsius
1: ûF Fahrenheit
[Description:]
When setting
C11
is linear, Ò-----Ó is displayed and setting
cannot be performed.
0
C 12
12
PV2 temperature unit
0 to 2
A setting of 0 means no decimal point and a setting of 1 and 2
indicates the number of decimal digits.
[Description:]
When setting
C11
is linear, Ò-----Ó is displayed and setting
cannot be performed.
The setting range varies with the
C11
and
C12
setting.
¥ A setting between 0 and 2 can be made when
C11
is set to:
5, 15, 65 to 69, 97 to 101 and
C12
is set to 0.
C11
settings: 66, 68, 69, 98, 100, 101 and
C12
is set to 1.
¥ A setting of 0 and 1 can be made when
C11
is set to: 0 to 5,
7, 8, 10, 12 to 14, 16, 64, 65, 67, 70, 71, 96, 97, 102, 103
and
C12
is set to 1.
¥ Only a setting of 0 is possible when
C11
is set to: 6, 9, 11
and
C12
is set to 1 .
¥ When the
C11
setting is for t/c or RTD, this setting is
reflected in PVU (PV2) units.
1
C 13
13
PV2 decimal point position
0 to 4
A setting of 0 means no decimal point and a setting
between 1 and 4 indicates the number of decimal digits.
[Description:]
C11
settings for t/c and RTD display Ò-----Ó and setting
cannot be performed.
When setting
C11
is linear, this setting is reflected in
PVU (PV2) units.
1
C 14
14
PV2 linear decimal point
position
Ð19999 to +20000 PVU (PV2)
[Description:]
C11
settings for t/c and RTD display Ò-----Ó and setting
cannot be performed.
Reversing the lower limit and upper limit makes it
possible to reverse analog inputs and specified values.
0 PVU
C 15
15
PV2 linear range lower limit
10000PVU
C 16
16
PV2 linear range upper limit
0: Yes (compensated internally)
1: No (compensated exernally)
[Description:]
C11
settings for t/c and RTD display Ò-----Ó and setting cannot
be performed.
0
C 17
17
PV2 cold junction
compensation
0: No
1: Yes
[Description:]
C11
settings for t/c and RTD display Ò-----Ó and setting
cannot be performed.
0
C 18
18
PV2 square root extraction
0.2 to 10.0 % (ratio depends on input range)
[Description:]
C11
settings for t/c and RTD display Ò-----Ó and setting
cannot be performed.
0.2
C 19
19
PV2 square root extraction
dropout
Ð1.0 to +1.0 ûC
[Description:]
C11
settings for t/c and RTD display Ò-----Ó and setting
cannot be performed.
Use 0.0 for normal settings.
0.0
C 20
20
PV2 cold junction bias
7-22