Chapter 8. PROGRAM SETUP
■
Setting event items
HANDLING PRECAUTIONS
Note that when setup data
C57
is set to 1, event items on the programming map
are skipped and not displayed.
●
When the event is a PV event
(1) In the set value display state, move to the segement event item to be set on the
programming map.
(2) Press the
ENTER key
to make display panel 1 flash (registration of first setting).
(3) Use the
↑
,
↓
,
←
, and
→
keys
to make the first setting – setting the event operating
point.
Setting range : OFF –19999 to +20000 SPU
: OFF 0 to 20000 SPU (for absolute value deviation events)
: OFF –5.0 to +105.0% (for MV events)
(4) Press the
ENTER key
to stop the flashing on display panel 1. (Pressing the
FUNC
and
CLR keys
causes display panel 1 to return to unset state “-----” and the
flashing stops.)
●
Display (PV events)
Unset values are indicated as “ ----- ”.
NOTE
A PV event setting consists of a setting (including OFF) and a subfunction. A subfunc-
tion cannot be used when a setting has not been made “ ----- ”.
8-7