Item
Specifications
Program
section
Input section
No. of programs
99 programs
No. of segments
99 segments/1 program, or total 2000 segments
Segment time
0 to 500 hours 00 min, 0 to 500 min 00sec, or 0.0 to 3000.0sec (Time unit is switchable.)
Segment slope
1 to 10000U/hours, 1 to 10000U/min, or 1 to 10000U/sec (Time unit is switchable.)
No. of sub-function
4000 settings
Event (16 point)
Operating point set as specified by event type.
PID group setting
Group 0 (continuing from previous segment), groups 1 to 9, group A (automatic
changeover) and ON-OFF control settable.
Output limiter group
Group 0 (continuing from previous segment), groups 1 to 9 settable
G.SOAK
Type (start point, end point, all) and G.SOAK width 0 to 1000U settable
PV shift
-10000 to +10000 settable
Repeat
Return segment number and repeat count settable.
PV start
Type settable for each program (ascending, descending and bi-directional)
Cycle
Cycle count number settable for each program
Pattern link
Program numbers 0 to 99 (program 0 without link) settable for each program
Tag
8 characters consisting of alphanumerics, katakana and symbols settable for each program
Basic time accuracy
–0.01% (segment time setting = 0, repeat; each cycle and repeat slows the process by 0.1sec)
Input type
Input sampling cycle
0.1s
Measurement current
RTD input: approx. 1mA, Current input on terminal A. (under operating conditions)
Max. allowable input
Thermocouple, DC voltage input:-5 to +15Vdc
DC current input : 50mAdc, 2.5Vdc
Burn out
Burnout on/off selectable
Range over assessment
100% FS or more: upscaled
-10% FS or less : downscaled
(However, inputs in the F50 range are not downscaled.)
Sub-function function
Event, PID group, output limiter group, G.SOAK, PV shift, repeat
1 to 10000U/1 pulse
Segment SP
Input impedance
DC current input: approx. 50 (under operating conditions)
Allowable parallel resistance
Thermocouple disconnection detection allowable parallel resistance : Higher than 1M
Resistance temperature
detector input
Cold junction compensation accuracy
0.5 (under standard conditions)
Influence of wiring
resistance
The ranges except F01, F33, P01, and P33 are lower than 85 .
(Includes the zener barrier resistor value. However, spot adjustment is needed.)
The ranges of F01, F33, P01, and P33 are lower than 10 .
(Zener barrier cannot be used.)
Thermocouple, DC voltage input:
Resistance temperature detector input:
Thermocouple
DC voltage (lower than 1V range)
DC voltage (5V range)
DC voltage (10V range)
Max. 0.01% FS/
within wire resistor 0 to 10W
The ranges of F01, F33, P01, and P33 are Max. 0.02% FS/
.
: 0.5 V/
: 0.5 V/
: 3 V/
: 6 V/
Segment setting system
RAMP-X: Setting by set points (SP) and time.
RAMP-T: Setting by set points (SP) and slope ( ).
RAMP-E: Setting by set points (SP) or SP per pulse of external switch input.
Input bias current
Thermocouple, DC voltage input: Max. 1.3 A (peak value, under standard
conditions). The range higher than 1V is Max. -3 A.
Thermocouple
K,E,J,T,B,R,S (JIS C1602-1981)
WRe5-26 (Hoskins Data)
PR40-20 (Johnson Matthey Data)
N (N.B.S. Monograph 161)
PLII (Engelhard Industries Data (IPTS68))
Ni-NiMo (General Electric Data)
Gold iron chromel (Hayashidenko Data)
Resistance temperature detector (RTD)
Pt100,JPt100 (JIS C1604-1989)
DC current
4 to 20mA, 2.4 to 20mA
DC voltage
0 to 10mV, -10 to +10mV, 0 to 100mV,
0 to 1V, -1 to +1V, 1 to 5V, 0 to 5V, 0 to 10V
Multi-range of thermocouple, Resistance temperature detector, DC voltage,
and DCcurrent(see page 2-8, 2-9)
Chapter 11. SPECIFICATIONS
11-1 Specifications
11-1