Chapter 7. PARAMETER SETUP
■
Detailed information on variable parameters
●
PA01
(keylock)
0: keylock disabled
1: display of setup data setting disabled
2: display of all settings disabled
3: display of all settings disabled. Operation keys disabled
• The following keys are disabled when
PA01
is set to 1.
Normal display mode:
SETUP key
(setup data setting)
FUNC + CLR + MESSAGE keys
(general reset)
• The following keys are disabled when
PA01
is set to 2.
Normal display mode:
SETUP key
(setup data setting)
FUNC + CLR + MESSAGE keys
(general reset)
FUNC + PARA keys
(event configuration data setting)
PID key
(PID parameter setting/constant value con-
trol data setting)
FUNC + PID keys
(constant value control data setting)
FUNC + PROG keys
(program setting)
↑↑
+ PROG keys
(program copy)
LOAD key
(memory card load)
SAVE key
(memory card save)
• The following keys are disabled when
PA01
is set to 3 or to 2.
Normal display mode:
PROG key
(program selection)
RUN/HOLD key
(RUN operation/HOLD operation)
PROG + RUN/HOLD keys
(RESET operation)
PROG + DISP keys
(ADV operation)
FUNC +
→
→
keys
(FAST operation)
A/M key
(AUTO operation/MANUAL operation)
AT key
(AT start, AT cancel)
Note, however, that in the normal display mode in MANUAL mode MV (controller)
and SP (programmer) can be changed.
●
PA02
(memory protect)
0 : disabled
1 : program settings are protected
2 : setup, variable parameters and event configuration settings are protected
3 : setup, variable parameters, event configuration settings and program set-
tings are protected
4 : setup, variable parameters, event configuration settings and PID parameter
settings are protected
5 : program settings and all parameter settings are protected
• When
PA02
is set to ≠ 0 (protect on), a general reset cannot be performed.
7-9