Chapter 12. CALIBRATION
■
Current output calibration
Scroll
↑
,
↓
,
←
, or
→
keys
to show (
6.0.6.6.
) on the upper display, then press
ENTER key
.
Connect the digital ammeter across terminals (See Figure 12-9).
●
OUT CH1 output calibration
(1) Press
SETUP key
until the PROG/SEG display shows (
06-01
).
Scroll
↑
,
↓
,
←
, or
→
keys
until meter indicates 4.00mA, then press
ENTER key
.
(2) Press
SETUP key
until the PROG/SEG display shows (
06-02
).
Scroll
↑
,
↓
,
←
, or
→
keys
until meter indicates 20.00mA, then press
ENTER key
.
●
OUT CH2 output calibration
(1) Press
SETUP key
until the PROG/SEG display shows (
06-03
).
Scroll
↑
,
↓
,
←
, or
→
keys
until meter indicates 4.00mA, then press
ENTER key
.
(2) Press
SETUP key
until the PROG/SEG display shows (
06-04
).
Scroll
↑
,
↓
,
←
, or
→
keys
until meter indicates 20.00mA, then press
ENTER key
.
●
AUX CH1 output calibration
(1) Press
SETUP key
until the PROG/SEG display shows (
06-05
).
Scroll
↑
,
↓
,
←
, or
→
keys
until meter indicates 4.00mA, then press
ENTER key
.
(2) Press
SETUP key
until the PROG/SEG display shows (
06-06
).
Scroll
↑
,
↓
,
←
, or
→
keys
until meter indicates 20.00mA, then press
ENTER key
.
●
AUX CH2 output calibration
(1) Press
SETUP key
until the PROG/SEG display shows (
06-07
).
Scroll
↑
,
↓
,
←
, or
→
keys
until meter indicates 4.00mA, then press
ENTER key
.
(2) Press
SETUP key
until the PROG/SEG display shows (
06-08
).
Scroll
↑
,
↓
,
←
, or
→
keys
until meter indicates 20.00mA, then press
ENTER key
.
12-15