SAFETY DEVICES
The safety devices must be dimensioned and installed according to EN 12828 !
The safety valve in the boiler circulation serves as a final safety device against malfunctions of the
equipment.
All legal safety regulations must be adhered to on-site via the authorised specialist company.
Earthing or potential equalisation must be carried out on the whole heating system according to EN 60204-1
by an authorised specialist company.
1 Safety temperature limiter
If the boiler temperature exceeds 95 °C, the
equipment must be switched off for safety
reasons.
The safety temperature limiter (STL) will lock in
this case.
Possible causes may be:
◼
Performance decrease in the boiler was
interrupted abruptly. This can occur due to
the switching off a pump or sudden
shutting of the heating circuit mixer.
◼
The load pumps are being controlled by
the HERZ Control. The so-called excess
temperature
flue
gas
would
be
automatically activated by the HERZ
Control.
This
avoids
higher
boiler
temperatures.
◼
The boiler is too large.
◼
The fuel level is set too high.
◼
Loss of power supply
◼
Etc.
At First the cause of the failure must be found and
be corrected, afterwards the safety temperature
limiter can be unlocked.
The boiler temperature must be lower than 75
°C before unlocking.
Only then the problem can be acknowledged. For
this purpose, the cover of the STL is screwed off.
The STL can be unlocked by a light pressure with
a sharp object. After unscrewing the cover the
fault acknowledgement must be performed at the
switch box. The location of the STL is on the left
side next of the display.
2 Burn-back safety unit
The burn-back safety (BBP) unit prevents a burn-
back into the fuel storage room. It separates
additionally the combustion chamber and the fuel
storage room. The burn-back safety unit (or cell
wheel sluice) is conducted like a fire flap. It opens
only when fuel is fed to the boiler.
3 Safety valve
The safety valve automatically releases, when the
pressure or temperature exceeds preset limits.
The safety valve has to release at the maximum
allowable pressure (according to boiler plate).
4 Safety heat exchanger (depending on the
type)
The safety heat exchanger is a built in safety
device and has to be connected to a thermal
release valve and installed, according to applied
standards. The safety heat exchanger has to be
connected directly to a cold water pipe (pressure
≤ 3 bar)
5 Ash container safety device
The ash container door is connected contact-free
(inductive sensor) to the boiler.
Fuel storage room temperature monitoring
The fuel storage room temperature monitoring is
placed directly above the transport screw. There
is placed a temperature sensor which is setting to
the release temperature. If the storage room
temperature exceeds its preset limit, the boiler will
switch to the operate condition „HEATING OFF“
and displays a fault report. Additionally a fault
sensor output gets active. Conduct alerting in
accordance with national standards.
Summary of Contents for pelletstar CONDENSATION 10
Page 1: ...OPERATING INSTRUCTIONS Pellet boiler pelletstar CONDENSATION 10 60 ...
Page 86: ...15 Annex 86 Hydraulic recommendation 2 ...
Page 87: ...Annex 15 87 15 2 Solar module schematic representation Program 1 ...
Page 88: ...15 Annex 88 Program 2 ...
Page 89: ...Annex 15 89 Program 3 ...
Page 90: ...15 Annex 90 Program 4 ...
Page 91: ...Annex 15 91 Program 5 ...
Page 92: ...15 Annex 92 Program 6 ...
Page 93: ...Notes 16 93 16 NOTES ...