T-CONTROL
9
45
Term
Description
Unit
Time 1
1 - 3 times can be set. The second and third time can be added by the +.
Example:
▪
time 1:
08:00
– 10:00
▪
time 2:
15:00
– 21:00
▪
time 3:
00:00
– 00:00
-
08:00
– 11:00
Setting up individual hot water tank loading times of every weekday
-
By pressing the symbol Monday preset gets assigned to remaining
weekdays
-
Barrier times
4 5
Time 1
1 - 2 times can be set. The second time can be added by the +. Example:
see time program.
-
08:00
– 11:00
Setting up individual hot water tank loading times of every weekday,
when it will be not heated
-
By pressing the symbol Monday preset gets assigned to remaining
weekdays.
-
Menu "Heat curve"
Heat curve 1
1
2
Heat curve
-
Heat curve 2
1
2
Flow max.
temperature
Setting up the maximum flow temperature (30-95) of chosen heating
circuit.
°C
Root point
temperature
Setting up the minimum flow temperature (20-70) of chosen heating
circuit
°C
Flow temperature at
+10°C
Setting up the flow temperature (20-90) of chosen heating circuit at
+10°C outside temperature
°C
Flow set temperature
at adjustable outside
temperature
Setting up the flow temperature (25-95) of chosen heating circuit at a
adjustable outside temperature
°C
Adjustable outside
temperature
Setting up the outside temperature (-20 - 0) of chosen heating circuit
regarding flow must temperature
°C
Switch off temperature
Setting up the outside temperature (5-40) at which the chosen heating
circuit switches off if this temperature is exceeded.
°C
Operation mode „Screed drying“
After „Screed drying“ mode selection the shown flow temperature sequence (see fig. 9.1) gets started
immediately. If a lower flow temperature is desired, the flow temperature can be set up with the parameter
„Flow max. temperature“. If screed drying is interrupted caused by a fault (power breakdown, etc.), the
program (after fault correction) continues drying as shown in table 9.1 automatically. A optional continuing
day can be selected with pa
rameter „Screed days“. After screed drying completion the boiler will switch to
"heating time mode". The desired temperature can be set for each day (end of the program with setpoint=
0°C).
Summary of Contents for pelletstar CONDENSATION 10
Page 1: ...OPERATING INSTRUCTIONS Pellet boiler pelletstar CONDENSATION 10 60 ...
Page 86: ...15 Annex 86 Hydraulic recommendation 2 ...
Page 87: ...Annex 15 87 15 2 Solar module schematic representation Program 1 ...
Page 88: ...15 Annex 88 Program 2 ...
Page 89: ...Annex 15 89 Program 3 ...
Page 90: ...15 Annex 90 Program 4 ...
Page 91: ...Annex 15 91 Program 5 ...
Page 92: ...15 Annex 92 Program 6 ...
Page 93: ...Notes 16 93 16 NOTES ...