11
Maintenance schedule
78
Item
Procedure
Check fault recognition and fault report
Check
if
fault
report
e.g.:
ASH
CONTAINER FAULT is shown
Safety valve
Check safety valve tightness
System pressure
Check system pressure.
Minimum pressure: 1,5 bar (cold)
Maximum pressure: see boiler plate
Fire extinguisher
Check fire extinguisher securing and seal
as well as hose and nozzle (according to
national standard)
Ash storage
Ash has to be stored in a non-flammable,
air tight container till disposal.
Boiler room
Remove flammable materials, except
wood chips or pellets stored in a
appropriate container, from the operating
room
Fire protection
Check structural fire protection and fire
doors (e.g.: self-locking fire door)
Condensate and
flushing water
drainage or lifting
station (if
available)
drain line
Inspection and function control of the
lifting unit and the pump or the
condensate / flushing water drain
For longer drain lines, these must be
checked at regular intervals and, if
necessary, cleaned by the customer.
Otherwise, there may be blockages in the
drainage area as deposits may not be
completely flushed away
Summary of Contents for pelletstar CONDENSATION 10
Page 1: ...OPERATING INSTRUCTIONS Pellet boiler pelletstar CONDENSATION 10 60 ...
Page 86: ...15 Annex 86 Hydraulic recommendation 2 ...
Page 87: ...Annex 15 87 15 2 Solar module schematic representation Program 1 ...
Page 88: ...15 Annex 88 Program 2 ...
Page 89: ...Annex 15 89 Program 3 ...
Page 90: ...15 Annex 90 Program 4 ...
Page 91: ...Annex 15 91 Program 5 ...
Page 92: ...15 Annex 92 Program 6 ...
Page 93: ...Notes 16 93 16 NOTES ...