11
Maintenance schedule
80
11.4
Annually inspection (service, notification)
Annually inspection, at least every 3000 operating hours.
Maintenance by manufacturers or certified sales partners
Item
Procedure
Maintenance
Conduct system maintenance by authorised
personnel
Burn back
protection device
(symbolic
representation)
Unscrew revision cover (depending on the
boiler type)
Check BFP flap visually for damages, wear
and tightness
Open BFP flap by using the aggregate test
Position paper strip between hopper flange
and BFP flap and close BFP flap afterwards.
Try to pull out paper strip. If possible, adjust
BFP flap.
Conduct paper strip test at different positions
ID-fan
Unscrew 4x wing nut
Remove and clean ID-fan witch a brush