10
Fault reports and their Fault reports and their corrections
68
No. Fault report
Cause of fault
Fault correction
001
BOILER SENSOR
Sensor break; Value outside the
measuring range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
002
COMBUSTION ROOM
SENSOR
Sensor break; Value outside the
measuring range
(0 - 1200°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
003
FLUE GAS SENSOR
Sensor break; Value outside the
measuring range
(-10 - 600°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
004
BACK FLOW SENSOR
Sensor break; Value outside the
measuring range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
005
STOKER SENSOR
Sensor break; Value outside the
measuring range
(-10 - 300°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
006
BURNING ROOM MAX
Combustion chamber temperature over
adjusted combustion chamber
temperature max.
adjust Combustion settings
✆
- contracting party
007
BUFFER SENSOR TOP
Sensor break; Value outside the
measuring range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
008
BUFFER SENSOR BOTTOM
Sensor break; Value outside the
measuring range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
009
WEATHER COMP. POWER
MAX.
Sensor break; Value outside the
measuring range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
010
BUFFER SENSOR MIDDLE
Sensor break; Value outside the
measuring range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
011
HOT WATER TANK
SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
Summary of Contents for pelletstar CONDENSATION 10
Page 1: ...OPERATING INSTRUCTIONS Pellet boiler pelletstar CONDENSATION 10 60 ...
Page 86: ...15 Annex 86 Hydraulic recommendation 2 ...
Page 87: ...Annex 15 87 15 2 Solar module schematic representation Program 1 ...
Page 88: ...15 Annex 88 Program 2 ...
Page 89: ...Annex 15 89 Program 3 ...
Page 90: ...15 Annex 90 Program 4 ...
Page 91: ...Annex 15 91 Program 5 ...
Page 92: ...15 Annex 92 Program 6 ...
Page 93: ...Notes 16 93 16 NOTES ...