Fault reports and their Fault reports and their corrections
10
69
No. Fault report
Cause of fault
Fault correction
012
CIRCULATION SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
013
HC-FLOW SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
014
HC-BACK FLOW SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
015
HC-ROOM SENSOR
Sensor break; Value outside the
measuring
range
(3 - 40°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
016
HC-ROOM CORR.
Sensor break; Value outside the
measuring
range
(-5 - +5)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
017
HC-OUTSIDE SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
018
SENSOR COLLECTOR
Sensor break; Value outside the
measuring
range
(-50 - 200°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
019
SENSOR COLLECTOR
BACK FLOW
Sensor break; Value outside the
measuring
range
(-50 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections, replace
as renew
✆
- contracting party
020
SENSOR SOLAR TANK1
Sensor break; Value outside the
measuring
range
(-100 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections, replace
as renew
✆
- contracting party
021
SENSOR SOLAR TANK2
Sensor break; Value outside the
measuring
range
(-50 - 200°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
022
SENSOR SOLAR RES.
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
▪
Check sensor, replace as renew
▪
Check plug, replace as renew
▪
Check wiring incl. connections, replace
as renew
▪
✆
- contracting party
Summary of Contents for pelletstar CONDENSATION 10
Page 1: ...OPERATING INSTRUCTIONS Pellet boiler pelletstar CONDENSATION 10 60 ...
Page 86: ...15 Annex 86 Hydraulic recommendation 2 ...
Page 87: ...Annex 15 87 15 2 Solar module schematic representation Program 1 ...
Page 88: ...15 Annex 88 Program 2 ...
Page 89: ...Annex 15 89 Program 3 ...
Page 90: ...15 Annex 90 Program 4 ...
Page 91: ...Annex 15 91 Program 5 ...
Page 92: ...15 Annex 92 Program 6 ...
Page 93: ...Notes 16 93 16 NOTES ...