Technical Data Manual

Biomass - Thermal Storage Tanks

for use with Biomass Boilers

5457 881  v1.5   06/2013  

Please file in Service Binder

IMPORTANT

Ensure that the lifting/handling equipment is able to 
securely handle the size and weight of this tank 
(see data on page 2). 
The floor where the tank is to be positioned must be able 
to properly support the weight of the tank filled with water.

Safety and Installation Requirements

Please ensure that these instructions are read and 
understood before starting any service work. Failure 
to comply with these instructions may cause product/
property damage, severe personal injury and/or loss of 
life.

Working on the equipment

The installation, adjustment, service and maintenance of 
this product must be performed by a licensed professional 
heating contractor who is qualified and experienced in the 
installation, service, and maintenance of hot water boilers. 
There are no user serviceable parts on the tanks.

Refer to the Installation and Start-up/Service 
Instructions applicable to this boiler.

Ensure that main power to the equipment being serviced 
is off.

Take precautions to avoid accidental activation of power 
during service work.

Do not perform service work on any component part 
without ensuring safe operation of the heating system. 
When replacing parts, use original Viessmann or 
Viessmann approved replacement parts.

Product Information

ASME ‘U’ code symbol stamped, pressure vessel with 
a Canadian Registration Number (CRN). When used in 
conjunction with Biomass boilers, the Biomass Thermal 
Storage Tank acts as a thermal reservoir and as a 
hydraulic break, decoupling boiler and the heating circuit 
from each other. 

Heat may be added to the tank by the biomass boiler 
or back-up systems and removed by the distribution 
system at different rates. This ensures steady supply 
temperatures to the heating system and ensures efficient 
energy use.

The tanks are equipped with three or five temperature 
sensors connected to the boiler control to regulate the 
biomass boiler operation.

Boiler model, size

Tank USG (L)

Pyrot 150

 400 (1514)

Pyrot 220

 530 (2006)

Pyrot 300

 700 (2650)

Pyrot 400

1000 (3785)

Pyrot 540

1500 (5678)

Pyrotec 390

1000 (3785)

Pyrotec 530

1500 (5678)

Pyrotec 720

1750 (6624)

Pyrotec 950

2500 (9464)

Pyrotec 1250

3300 (12492)

Summary of Contents for Pyrot 150

Page 1: ...iler Ensure that main power to the equipment being serviced is off Take precautions to avoid accidental activation of power during service work Do not perform service work on any component part without ensuring safe operation of the heating system When replacing parts use original Viessmann or Viessmann approved replacement parts Product Information ASME U code symbol stamped pressure vessel with ...

Page 2: ...12 30 18 46 9 23 41 104 10 25 17 43 24 61 31 79 38 97 21 53 1000 1500 680 1000 3785 54 137 121 307 88 224 12 30 18 46 9 23 72 183 10 25 25 64 40 102 55 140 70 178 21 53 1500 2400 1089 1500 5678 66 168 124 315 88 224 14 35 19 48 7 18 81 206 12 30 25 64 38 97 51 130 64 163 24 61 1750 2700 1225 1750 6624 72 183 121 307 84 213 15 38 20b 525 11 28 66 168 12 30 25 64 38 97 51 130 64 163 27 69 2500 3500 ...

Page 3: ...000 Full P R V S1 1 Coupling N P T 3000 Full Sensor Well S2 1 Coupling N P T 3000 Full Sensor Well S3 1 Coupling N P T 3000 Full Sensor Well S4 1 Coupling N P T 3000 Full Sensor Well S5 1 Coupling N P T 3000 Full Sensor Well T1 1 Coupling N P T 3000 Full Temperature Gauge T2 1 Coupling N P T 3000 Full Temperature Gauge T3 1 Coupling N P T 3000 Full Temperature Gauge Connection Sizes Model No DV N1...

Page 4: ...pipe must be installed in the shortest distance and pitch downward from the pressure relief valve and terminate plain Ensure the pressure relief valve is adequately secured WARNING The discharge pipe for the pressure relief valve must be oriented to prevent scalding of attendants Never pipe the discharge pipe to the outdoors WARNING Do not install an isolation valve or any kind of an obstruction b...

Reviews: