English (GB)
15
7.3 Electrical connection
The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the
electricity supply on which it will be used.
All cables/wires must be fitted through the cable entries and
gaskets (IP65).
The power supply socket must be placed near the cabinet as the
controller is supplied with a 1.5 m cable, a Schuko plug for
single-phase and a CEE plug for three-phase pumps.
Maximum backup fuse is stated on the controller nameplate.
If required according to local regulations, install an external mains
switch.
7.4 Setting of LC 220
LC 220 has a 4-contact DIP switch. See fig.
To make the settings, open the cabinet cover by means of the
bayonet fastener locks. The locks on the left side have hinge
strings.
The DIP switch has the following functions:
• setting of start level (switch 1). The factory setting is set to
inlet 250 mm above the floor to get the highest effective tank
volume. For floor standing toilets, the setting must be changed
to 180 mm. Starts and stops will be adjusted automatically.
• selection of automatic alarm resetting (switch 2)
• selection of service interval (switch 3)
• selection of sensor (switch 4).
The DIP-switch factory setting is shown in fig.
Each individual switch (1 to 4) of the DIP switch can be set to
position OFF or ON.
When the DIP-switch setting is changed, the controller must be
switched off for at least 10 seconds!
Set the switches 1 to 4 as follows:
•
Switch 1
(start level):
•
Switch 2
(automatic alarm reset):
•
Switch 3
(service interval):
•
Switch 4:
(sensor resetting):
Fig. 16
DIP switch
Warning
LC 220 must be connected in accordance with the
rules and standards in force for the application in
question.
Warning
Before opening the cover, switch off the mains
supply.
Note
During setting, the controller must be off circuit for at
least 10 seconds to ensure the correct configuration
during startup after change of the DIP-switch setting.
Pos.
Description
ON
The pump starts when the level in the collecting tank
reaches 250 mm.
OFF
The pump starts when the level in the collecting tank
reaches 180 mm.
Pos.
Description
ON
The fault indication will be reset after the fault has
disappeared, meaning the indicator lights will be turned
to off and the alarm signals to external alarm devices
and the built-in buzzer will be deactivated.
OFF
The alarm signal must be reset manually by switching
the selector switch to position "0".
Pos.
Description
ON
The function for reminding that it is time for
maintenance is activated. The yellow indication light will
be on when it is time for maintenance work.
The maintenance interval is 1 year (fixed value).
OFF
The function for reminding that it is time for
maintenance is deactivated.
Pos.
Description
ON
Safe (normal position, factory default)
OFF
Switch briefly to OFF for the sensor to adjust to the
ambient pressure. See service instructions.
T
M
05
14
04
27
11
HIGH
LOW
Summary of Contents for Multilift MSS
Page 2: ...2...
Page 4: ...Table of contents 4 Multilift MSS UA 366 CN 381 Appendix 396...
Page 25: ...BG 25 5 2 2 8 ON OFF AUTO I O AUTO 8 1000 mm DIP EN 12056 4 TM05 3455 0616...
Page 145: ...GR 145 5 2 2 8 ON OFF AUTO AUTO LED 8 1000 mm DIP H EN 12056 4 TM05 3455 0616...
Page 371: ...UA 371 5 2 2 8 ON OFF AUTO I O AUTO 8 1000 DIP EN 12056 4 TM05 3455 0616...
Page 386: ...CN 386 5 2 1 LC 220 4 5 2 2 8 ON OFF AUTO I O AUTO LED 8 1000 mm DIP EN 12056 4 TM05 3455 0616...
Page 397: ...397...
Page 398: ...398...