GREE GMV5 HR HEAT RECOVERY UNITS
283
PART 3 KEY PARTS MAINTENANCE
1 CAUTIONS ON CONTROLLER AP1
REPLACEMENT
1.1 Cautions on ODU AP1 Replacement
1.1.1 Distinguishing Master Module from Slave Module
Before replacing ODU AP1, determine the module is a master ODU or a slave ODU. They can be
distinguished based on:
(1)
“Master module DIP state (SA8_MASTER-S)”
Every cooling system has only one master module (set in power-
off state). When a DIP is “ON”, the
corresponding position is “0”; when the DIP is “OFF”, the corresponding position is “1”. If
SA8_MASTER-
S is set to “00”, it indicates a master module; if it is set to “10”, it indicates a slave module
(as shown in the figure below).
DIP setting
position
DIP setting
position
DIP setting
position
DIP setting
position
Master module state
Slave module state
(2) AP1 LED
When a master module is powered on, LED1 is displayed as “01”. For a slave module, LED1 is
displayed as “02”, “03” or “04” (as shown in the figure below).
LED1 display state
Master module state
LED1 display state
Slave module state
LED1 display state
Slave module state
LED1 display state
Slave module state
Or
Or
1.1.2 Cautions on Replacement of Master ODU AP1
Before replacing master module AP1, make the following preparations:
(1) Master module DIP setting
Set the new AP1 identical to the faulty AP1. Note that settings must be performed when the master
ODU is powered off and they will take effect after the ODU is powered on. Settings that are performed in
power-on state are invalid.
(2) Communication state check
After AP1 DIP setting and all wiring, power on the master ODU AP1 and check whether D3 and D4
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...