GREE GMV5 HR HEAT RECOVERY UNITS
10
No.
Name
Main Function
10
Four-way valve
Used for the switching between the cooling and heating
functions of system IDU.
11
Heat exchanger
Used for outdoor heat exchange.
12
Fan
Strengthens heat exchanging.
13
Defrosting temperature sensor
Used for defrosting detection.
14
Electronic expansion valve for heating
Controls refrigerant adjustment in heating mode.
15
High height difference valve
It‘s the pressure-drop device when the height difference
between indoor unit and outdoor unit is big.
16
One-way valve
Controls refrigerant flow direction.
17
Sub cooler electronic expansion valve
Controls the degree of sub cooling of tube refrigerant when the
system is running in cooling mode, and reduces the capacity
loss on pipes.
18
Sub cooler
Controls the degree of sub cooling of tube.
19
Liquid outlet temperature sensor of sub
cooler
Detects tube temperature.
20
Inlet temperature sensor of gas-liquid
separator
Detects the inlet temperature of gas-liquid separator to prevent
the system from running when the refrigerant flows back to the
compressor.
21
Gas outlet temperature sensor of sub
cooler
Detects gas temperature of sub cooler.
22
Low-pressure sensor
Detects system low pressure to avoid extra-low operating
pressure.
23
Gas-liquid separator
Separate gas and liquid to prevent the system from running
when the refrigerant flows back to the compressor.
24
Outlet temperature sensor of gas-liquid
separator
Detects internal status of gas-liquid separator to further control
the compressor suction performance.
25
Liquid intake valve
Liquid intake control valve for refrigerant adjustment tank
26
Pressure valve
Pressure control valve for refrigerant adjustment tank
27
Pressure balance valve
Press control valve inside the refrigerant adjustment tank
28
Drain valve for cooling
Drainage control valve for cooling of refrigerant adjustment tank
29
Drain valve for heating
Drainage control valve for heating of refrigerant adjustment tank
30
Dry strainer
Avoid impurities getting into the electric parts. Meanwhile,
absorb the water inside the liquid status to prevent ice
blockage.
31
Filter
Prevents impurities from entering components and parts.
32
Capillary tube
Supports flow regulating and pressure reduction.
33
One-way valve
Avoid impurities getting into the electric parts. Meanwhile,
absorb the water inside the liquid status to prevent ice
blockage.
34
One-way valve
Prevent the refrigerant inside the liquid valve flow into the
refrigerant adjustment tank from heating drain valve.
35
Liquid valve
Stop valve, closed when the unit is delivered from the factory
and will be opened after installation.
36
Low pressure gas pipe valve
Stop valve, closed when the unit is delivered from the factory
and will be opened after installation.
37
High pressure gas pipe valve
Stop valve, closed when the unit is delivered from the factory
and will be opened after installation.
38
Low-pressure measurement valve
Detects the low pressure value or charges refrigerant during
system running.
39
Unloading valve
Opening if the pressure inside the liquid pipe is too high
40
Oil return solenoid valve
Oil return control for the compressor
41
Gas-bypass valve
Make sure pressure of the system is balanced
42
Pressure-balanced valve
Ensures success startup of compressor.
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...