GREE GMV5 HR HEAT RECOVERY UNITS
120
"0075" is displayed.
If no button operations are performed on the master unit for five minutes, the function setting
automatically quits and the unit restores the current status.
Note:
The online IDU quantity query function applies to a single refrigerating system only.
Step 7: If the n6 fault query is selected, the display is as follows. Enter the to-be-confirmed status of
fault query.
LED1
LED2
LED3
Function Code
Display Mode
Current
Progress/Mode
Display Mode
Current Status
Display Mode
n6
Blinking
00
Blinking
00
Blinking
Press "SW7" on the master unit to confirm fault query.
Select a fault to be queried by pressing "SW1 (UP)" or "SW2 (DOWN)". LED3 alternately displays
the historical fault code and module address in an interval of one second in the sequence of fault records.
LED2 displays the fault sequence number. If there not historical faults, LED2 and LED3 display “00” by
default. Up to five historical faults can be queried. The faults that can be queried are as follows:
Code
-
Code
-
E1
High-pressure protection
P9
Inverter compressor out-of-step protection
E3
Low-pressure protection
C2
Communication failure between the master unit
and inverter compressor driver
U4
Lack of refrigerant protection
P8
Over-high temperature protection for inverter
compressor driver module
E2
Discharge low-temperature protection
P7
Temperature sensor failure of inverter
compressor driver module
J9
Over-low pressure ratio protection
PF
Charge circuit failure of inverter compressor
driver
J8
Over-high pressure ratio protection
HL
DC bus line over-low voltage protection for
inverter outdoor fan driver
J7
Gas-mixing protection of 4-way valve
HH
DC bus line over-high voltage protection for inverter
outdoor fan driver
E5
High-temperature protection of compressor 1
H6
Inverter outdoor fan driver IPM module protection
E6
High-temperature protection of compressor 2
HJ
Inverter outdoor fan startup failure
J2
Over-current protection of compressor 2
HE
Inverter outdoor fan phase lack protection
EU
Top high-temperature protection of compressor
1
H3
Inverter outdoor fan driver module reset
Eb
Top high-temperature protection of compressor
2
H5
Inverter outdoor fan over-current protection
PL
DC bus line over-low voltage protection for inverter
compressor driver
HC
Current detection circuit failure of inverter outdoor
fan driver
PH
DC bus line over-high voltage protection for
inverter compressor driver
H9
Inverter outdoor fan out-of-step protection
P6
Inverter compressor driver IPM module
protection
C3
Communication failure between the master unit
and inverter outdoor fan driver
PJ
Inverter compressor startup failure
H8
Over-high temperature protection for inverter
outdoor fan driver module
PE
Inverter compressor phase lack protection
H7
Temperature sensor failure of inverter outdoor fan
driver module
P3
Inverter compressor driver module reset
P5
Inverter compressor over-current protection
PC
Current detection circuit failure of inverter
compressor driver
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...