GREE GMV5 HR HEAT RECOVERY UNITS
169
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
and the
difference
between the
compressor's
exhaust
temperature
or cover
temperature
and the
high-pressure
temperature
is smaller than
10°C
(
18
°F)
.
2.2 The body
of the
electronic
expansion
valve is not
working
properly.
Other reasons
2.2.1
Affected by
impurities in
the system
——
Clean the
system and
clear the
impurities.
Replace the
body of the
electronic
expansion
valve.
2.2.2 The
valve body is
faulty.
——
Replace the
body of the
electronic
expansion
valve.
3. Exhaust
temperature
sensor failure
——
——
——
——
——
Replace the
temperature
sensor or main
board.
4. Too much
refrigerant
Other
reasons
Incorrect
quantity of
refrigerant is
injected.
——
——
——
Check the
necessary
amount of
refrigerant
and discharge
the unneeded
refrigerant
slowly via the
stop valve of
the fluid pipe.
(2) Pressure exception
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
E1
High
pressure
protection
1. The stop
valve of the
ODU is not
fully
opened as
required.
——
——
——
——
Manual
check
Fully
open
the stop
valve.
2. The
system
pipeline is
blocked.
The system's
exhaust
pressure
rises and the
low pressure
is too low
(compared
with the
reference
value).
2.1. The
system gas
pipeline is
blocked.
Touch the
pipe along
the flowing
direction of
refrigerant to
feel the
temperature
difference.
The
difference is
large.
2.1.1 The
block is
caused by
solder.
Cut off the
pipe and
check it.
Replace
and
solder
the
pipe.
2.1.2 The
pipeline is
blocked by
impurities.
Replace
and
solder
the
pipe.
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...