3 CAUTIONS ON COMPRESSOR DRIVE
REPLACEMENT
(1) Disconnect the power supply of the system. Set a multimeter to the AC voltage gear and
measure voltage between two of the lines (L1, L2, L3, and N). The measuring result should be
0 V (sometimes, multimeters may be faulty and read false values). Set a mark beside the power
supply for warning.
(2) Measure compressor drive DC bus voltage between two wire terminals of P, U, V, W and N. Set
the multimeter to the DC voltage gear and measure the voltage between P and N. The voltage
should be lower than 36 V. If no multimeter is available, wait for 20 minutes before performing
the steps below.
(3) Disconnect all lines of the compressor drive, including: compressor line; communication line
between the master unit and the drive; communication line between the compressor drive and