GREE GMV5 HR HEAT RECOVERY UNITS
22
Outdoor Units_Heat Recovery
Ton
12
14
16
Model
-
GMV-Q144WM/B-U(U) GMV-Q168WM/B-U(U) GMV-Q192WM/B-U(U)
Module combination
-
GMV-Q72WM/B-U(U)
+GMV-Q72WM/B-U(U)
GMV-Q72WM/B-U(U)
+GMV-Q96WM/B-U(U)
GMV-Q96WM/B-U(U)
+GMV-Q96WM/B-U(U)
°F
-4~75.2
-4~75.2
-4~75.2
Refrigerant
Refrigerant Type
-
R410A
R410A
R410A
Refrigerant Charge
Volume
kg
9.6+9.6
9.6+11.2
11.2+11.2
lbs.
21+21
21+25
25+25
Control
-
EXV
EXV
EXV
Pipe
Connection
Low pressure Gas
Pipe Size
mm
28.6
28.6
28.6
in.
1 1/8
1 1/8
1 1/8
High pressure gas
pipe
mm
Φ22.2
Φ22.2
28.6
in.
7/8
7/8
1 1/8
Liquid Pipe Size
mm
12.7
15.9
15.9
in.
1/2
5/8
5/8
Dimensions
(width×depth
×height)
External Dimension
mm
1340×765×1605
+1340×765×1605
1340×765×1605
+1340×765×1605
1340×765×1605
+1340×765×1605
in.
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
52-3/4×30-1/8×63-1/5
+52-3/4×30-1/8×63-1/5
Packaging
Dimension
mm
1420×840×1775
+1420×840×1775
1420×840×1775
+1420×840×1775
1420×840×1775
+1420×840×1775
in.
55-7/8×33-1/8×69-7/8
+55-7/8×33-1/8×69-7/8
55-7/8×33-1/8×69-7/8
+55-7/8×33-1/8×69-7/8
55-7/8×33-1/8×69-7/8
+55-7/8×33-1/8×69-7/8
Weight
Net Weight
kg
305+305
305+315
315+315
lbs.
672+672
672+694
694+694
Gross Weight
kg
320+320
320+330
320+330
lbs.
705+705
705+728
728+728
Maximum qty of connected indoor
units
unit
23
29
33
Protection
Devices
High Pressure
Protection
High pressure sensor, High pressure switch
Compressor /Fan
Over-current protection, Over-heat protection
Inverter
Over-current protection, Over-heat protection, High/Low voltage protection,
Remark
It refers to the operation power of compressor under ARI test conditions (Condensing temp. 130°F;
Evaporating temp.45°F; Return gas temp.65°F; Liquid temp.115°F) at 60Hz.
Oil charge includes the total oil amount of outdoor units, residual oil amount of compressor and oil
separate tank. When replacing the compressor or oil separate tank, only the corresponding required oil
amount shall be charged.
Outdoor Units_Heat Recovery
Ton
18
20
22
Model
-
GMV-Q216WM/B-U(U) GMV-Q240WM/B-U(U) GMV-Q264WM/B-U(U)
Module combination
-
GMV-Q96WM/B-U(U)
+GMV-Q120WM/B-U(U)
GMV-Q120WM/B-U(U)
+GMV-Q120WM/B-U(U)
GMV-Q72WM/B-U(U)
+GMV-Q96WM/B-U(U)
+GMV-Q96WM/B-U(U)
Performance
Nominal Cooling
Capacity
Btu/h
216000
240000
264000
kW
63.3
70.3
77.4
Rated Cooling
Capacity
Btu/h
201000
222000
247000
Nominal Heating
Capacity
Btu/h
243000
270000
297000
kW
71.2
79.1
87.1
Rated Heating
Capacity
Btu/h
226000
252000
275000
Cooling Power Input
kW
7.30+9.58
9.58+9.58
5.45+7.30+7.30
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...