GREE GMV5 HR HEAT RECOVERY UNITS
202
2.2.4
.26 “bA” Malfunction of oil-return temperature sensor
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason:
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting:
2.2.4.27
“C0” IDU and ODU, IDU wired controller communication error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If no communication between ODU and IDU or between IDU and wired controller in continuous 30s,
report the error.
Possible reason:
■Communication wire is connected improperly or loose
■Communication wire is cut off
■Communication wire is in poor connection