GREE GMV5 HR HEAT RECOVERY UNITS
185
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
5. The high
pressure
switch is
faulty.
E1 protection
is displayed
on the unit
when it is
powered on.
5.1 The high
pressure
switch is not
connected
to the main
board.
——
5.1.1 The
pressure
switch is not
connected to
the main
board.
——
Reconnect it.
——
5.1.2 The
connect wire
between the
pressure
switch and
main board is
faulty.
——
Reconnect
them with the
wire.
5.2 The high
pressure
switch is
damaged.
——
——
——
Replace the
pressure
switch.
6. The fan is
not working
properly.
A. The
ODU's fan
does not
work in the
cooling
mode. B.
The IDU's
motor does
not work in
the heating
mode.
6.1 The
IDU's fan is
faulty.
Manual check
6.1.1 The
power cable
connecting
the motor
and main
board is
loose.
Manual check
Reconnect the
motor with the
power cable.
6.1.2 The
electric
capacity is
not
connected or
is damaged.
Manual check
Connect or
replace the
electric
capacity.
6.1.3 The
motor is
damaged.
Other reasons
Replace the
motor.
6.2 The
ODU's fan is
faulty.
Manual check
6.2.1 The fan
motor is not
properly
connected
with the
control board
of the motor
with the
power cable.
Manual check
Reconnect it
properly.
6.2.2 The fan
motor is not
properly
connected
with the
control board
of the motor
with the
signal
feedback
cable.
Manual check
Reconnect it
properly.
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...