GREE GMV5 HR HEAT RECOVERY UNITS
9
2.3 Piping Diagram of GMV-Q168WM/B1-F(U)
2.4 Names and Main Functions of Components
No.
Name
Main Function
1
Compressor
Adjusts its own rotational speed based on the actual
requirement of the system to implement capacity control.
2
Compressor heat tape
Maintains a proper oil temperature in the compressor when the
compressor is in standby status, ensuring the reliability during
compressor startup.
3
Compressor casing-top temperature
sensor
Detects a compressor's exhaust gas temperature for
compressor control and protection.
4
Exhaust pipe temperature sensor of
compressor
Detects a compressor's exhaust gas temperature for
compressor control and protection.
5
High-pressure circuit breaker
Protects a compressor by sending feedback signal to stop the
system when the compressor's discharge temperature exceeds
the operating value of high-pressure circuit breaker.
6
Oil extractor
Separates the gas and oil in the system to ensure compressor
reliability.
7
Oil temperature sensor
Detect the oil return temperature of compressor
8
One-way valve
Prevents high-pressure gas from entering the compressor and
fast balances the suction pressure and discharge pressure in a
compressor.
9
High-pressure sensor
Detects the high pressure value in the system in real time mode
for compressor protection and other control functions.
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...