GREE GMV5 HR HEAT RECOVERY UNITS
17
Outdoor Units_Heat Recovery
Ton
24
26
Model
-
GMV-Q288WM/B-F(U)
GMV-Q312WM/B-F(U)
Module combination
-
GMV-Q96WM/B-F(U)
+GMV-Q96WM/B-F(U)
+GMV-Q96WM/B-F(U)
GMV-Q96WM/B-F(U)
+GMV-Q96WM/B-F(U)
+GMV-Q120WM/B-F(U)
Performance
Nominal Cooling
Capacity
Btu/h
288000
312000
kW
84.4
91.4
Rated Cooling
Capacity
Btu/h
270000
291000
Nominal Heating
Capacity
Btu/h
324000
351000
kW
95.0
102.9
Rated Heating
Capacity
Btu/h
300000
326000
Cooling Power Input
kW
7.3+7.3+7.3
7.3+7.3+9.58
Heating Power Input
kW
7.85+7.85+7.85
7.85+7.85+10.42
Sound Pressure Level dB(A)
-
-
Power Supply
-
208/230V 3~ 60Hz
Compressor
Type
-
Inverter scroll type
Inverter scroll type
Number
N
1+1+1
1+1+2
Motor Output
①
kW
-
-
Starting Method
-
Inverter
Inverter
Operating Range
-
-
-
Refrigeration Oil
Brand
-
FVC68D or FV-68H
FVC68D or FV-68H
Fan
Type× Quantity
-
Propeller×
(
2+2+2
)
Propeller×(2+2+2)
Motor output
W
750×2+750×2+750×2
750×2+750×2+750×2
Starting method
-
Inverter
Inverter
Air flow rate
m
3
/h
14000+14000+14000
14000+14000+14000
cfm
8240+8240+8240
8240+8240+8240
Max. external static
pressure
Pa
82
82
in.W.G
0.328
0.328
Ambient
temperature
range
Cooling
°C
-5~52
-5~52
°F
23~125.6
23~125.6
Heating
°C
-20~24
-20~24
°F
-4~75.2
-4~75.2
Refrigerant
Refrigerant Type
-
R410A
R410A
Refrigerant Charge
Volume
kg
11.2+11.2+11.2
11.2+11.2+11.7
lbs.
24.69+24.69+24.69
24.69+24.69+25.79
Control
-
EXV
EXV
Pipe
Connection
Low pressure Gas
Pipe Size
mm
34.9
34.9
in.
1 3/8
1 3/8
high pressure gas
pipe
mm
28.6
28.6
in.
1 1/8
1 1/8
Liquid Pipe Size
mm
19.05
19.05
in.
3/4
3/4
Dimensions
(width×depth
×height)
External Dimension
mm
1340×765×1605+1340×765×1605
+1340×765×1605
1340×765×1605+1340×765×1605
+1340×765×1605
in.
52-3/4×30-1/8×63-1/5+52-3/4×30
-1/8×63-1/5+52-3/4×30-1/8×63-1/5
52-3/4×30-1/8×63-1/5+52-3/4×30
-1/8×63-1/5+52-3/4×30-1/8×63-1/5
Packaging
Dimension
mm
1420×840×1775+1420×840×1775
+1420×840×1775
1420×840×1775+1420×840×1775
+1420×840×1775
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...