GREE GMV5 HR HEAT RECOVERY UNITS
246
2.2.4.83
“H9” Desynchronizing protection of inverter compressor
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If H9 is displayed, it indicates
Desynchronizing protection of inverter compressor
Possible reason:
■Poor contact of fan UVW wire
■Fan is broken
■Fan blade is blocked (Fan blade is blocked and motor shaft is rusty)
■Fan drive board is abnormal
Troubleshooting:
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...