GREE GMV5 HR HEAT RECOVERY UNITS
97
PART 9 REFRIGERANT PERFUSION
1 CALCULATION METHOD FOR
PERFUSING REFRIGERANT
Outdoor unit has been charged refrigerant before delivery.
Charge additional refrigerant for field-installed connecting pipe. If the pipeline is longer than
1m(39-3/8inch), please refer to the following table for charging amount of refrigerant. (Liquid pipe
prevails)
How much additional refrigerant should be charged
Total refrigerant charging amount R= Pipeline charging amount A + ∑charging amount B of every
module
(1) Pipeline charging amount
Added refrigerant quantity A for piping = ∑Liquid pipe length × Added refrigerant quantity for each
meter(inch) of liquid pipe
Diameter of liquid pipe mm(inch)
28.6(1-1/8)
25.4(1)
22.2(7/8)
19.05(3/4)
15.9(5/8)
12.7(1/2)
9.52(3/8)
6.35(1/4)
kg/m
0.680
0.520
0.350
0.250
0.170
0.110
0.054
0.022
OZ/inch
0.61
0.47
0.31
0.22
0.15
0.10
0.05
0.02
(2)
∑Refrigerant charging amount B of every module
Refrigerant charging amount B of every module
kg(Pounds)
Rated Capacity(1000Btu/h)
IDU/ODU rated capacity
collocation ratio C
Quantity of included
IDUs(N)
72
96
120
144
168
50%≤C≤90%
N<4
0
0
0
0
1.5(3.3)
N≥4
0.5(1.1)
0.5(1.1)
0.5(1.1)
1(2.2)
3.5(7.7)
90%<
C≤105%
N<4
1(2.2)
1(2.2)
1.5(3.3)
2(4.4)
5.5(12.1)
8>
N≥4
3.5(7.7)
2(4.4)
3(6.6)
3.5(7.7)
6.5(14.3)
N≥8
4(8.8)
3.5(7.7)
5.5(12.1)
6.5(14.3)
8(17.6)
105%<
C≤135%
N<4
2(4.4)
2(4.4)
2.5(5.5)
3(6.6)
6.5(14.3)
8>
N≥4
4(8.8)
3.5(7.7)
4(8.8)
4.5(9.9)
8(17.6)
N≥8
4.5(9.9)
4.5(9.9)
6(13.2)
7 (15.4)
9(19.8)
For example:
The OUD is composed of 3 modules: 72kBtu/h, 120 kBtu/h and 120 kBtu/h. The IDUs are made up
of 7sets of 48 kBtu/h
IDU/ODU rated capacity collocation ratio C= 48×7/(72+120+120)=108%.The quantity of included
IDUs is more than 4 sets. Please refer to the above table.
Refrigerant charging amount B for 72 kBtu/h module is 4.0kg(8.8pounds).
Refrigerant charging amount B for 120 kBtu/h module is 4.0kg(8.8pounds).
Refrigerant charging amount B for 120 kBtu/h module is 4.0kg(8.8pounds).
So,
Σ Refrigerant charging amount B of every module=4.0+4.0+4.0=12kg (8.8+8.8+8.8
=26.4pounds).
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...