GREE GMV5 HR HEAT RECOVERY UNITS
183
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
4. Too much
refrigerant
Other reasons
Incorrect
quantity of
refrigerant is
injected.
——
——
——
Check the
necessary
amount of
refrigerant
and discharge
the unneeded
refrigerant
slowly via the
stop valve of
the fluid pipe.
2.2.2 Pressure exception
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
E1
High
pressure
protection
1. The stop
valve of the
ODU is not
fully opened
as required.
——
——
——
——
Manual check
Fully open the
stop valve.
2. The
system
pipeline is
blocked.
The system's
exhaust
pressure
rises and the
low pressure
is too low
(compared
with the
reference
value).
2.1. The
system air
pipeline is
blocked.
Touch the pipe
along the flowing
direction of
refrigerant to feel
the temperature
difference. The
difference is
large.
2.1.1 The
block is
caused by
solder.
Cut off the
pipe and
check it.
Replace and
solder the pipe.
2.1.2 The
pipeline is
blocked by
impurities.
Replace and
solder the pipe.
2.2 The fluid
pipe is
blocked.
Touch the pipe
along the flowing
direction of
refrigerant to feel
the temperature
difference. The
difference is
large or part of
the pipe is
frosting.
——
——
Replace and
solder the pipe.
2.4 The pipe
that
connects the
IDU is
blocked.
Touch the pipe
along the flowing
direction of
refrigerant to feel
the temperature
difference. The
difference is
large or part of
the pipe is
frosting.
2.4.1 The
block is
caused by
solder.
Cut off the
pipe and
check it.
Replace and
solder the pipe.
2.4.2 The
pipeline is
blocked by
impurities.
Replace and
solder the pipe.
Summary of Contents for GC201808-III
Page 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Page 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Page 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Page 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Page 362: ...JF00302879 ...