Precautions for Input/Outout communication
1.
Program selection
Make sure to select the program No.1 to No.24 for the program bit when the program selected.
When the program number is 0 or more than 25, it becomes ALC0 (Program not selected NG)
2.
Input ENABLE
Please always input “Input ENABLE” after the program bit is selected.
If ENABLE is not input, the program cannot be changed or selected, After the program selection is changed,
check that the output of program selection completion and the program number is security changed.
3.
Determination reset
Determination reset is not accepted except the total determination output after the program is finished.
(To prevent the double tightening, it is always required to input the determination reset
after the program is finished. (Total determination output))
4.
Inching start
Select the program number by selecting the program bit at the inching start.
Rotating speed and direction are decided during rotation by selecting the program.
(Rotation setting number is selected by the selected program number and the speed and rotating direction
by this setting controls the inching movement.)
If the program is not selected, inching start is not accepted. Please be careful of it.
Do not input the inching start during the program operation. It may cause malfunction.
5.
Alarm reset
Input for the alarm reset input is enabled only when the alarm occurred.
6.
IN input
Effective only when IN is set in the program setting.
If IN setting is performed in the program, make sure to enter IN because the program waits
for the input of IN after the program execution until the previous step before the IN is set.
Do not input the inching start and alarm reset. It may cause malfunction.
7.
Auto/Each selection
Auto selection
:
Only the start input is accepted. Do not turn OFF the start signal input until the total
determination is output. Doing so
causes “FFFF” NG. This is the interruption NG of the program while running.
Each selection: Only the inching start input is accepted. When the input signal is turned OFF after inching
started, it becomes to wait for the inching start and only operates when the inching star is turned ON.
8.
GSK reset
(
ALL reset
)
When GSK reset is input, make sure to input from the program selection because all steps return to the initial
status.
9.
Program bit selection
Program bit selection allows you to select the program number by combining the program bit.
10.
Program setting
Rating setting and axis number setting is possible by each block and axis unit in the program.
Summary of Contents for GSK Series
Page 1: ...Instruction Manual GSK GSKW Controller November 2017 GIKEN INDUSTRIAL CO LTD The 3rd edition...
Page 16: ...15 Size Interface dimensions Standard type GSK IF...
Page 17: ...16 Controller dimensions Standard type GSK 4 GSKW 4...
Page 18: ...17 Controller dimensions Standard type GSK 5 7...
Page 19: ...18 Controller dimensions T type GSK T5 T7...
Page 20: ...19 Controller dimensions Standard type GSKW 5...
Page 21: ...20 Controller dimensions T type GSKW T5...
Page 22: ...21 Dimensions display Model GSK D1 Panel cut out dimensions Back Side Front Under...
Page 24: ...23 M net ver GSK Controller system wiring reference diagram...
Page 28: ...27 External connection diagram I F unit Connected equipment standard and T type...
Page 50: ...49 Setting...
Page 58: ...57 Reverse tightening reference waveform...
Page 62: ...61...
Page 63: ...62 Gradient calculation method...