2-
22
LPS-D Line Protection System
GE Power Management
2.3 PROTECTION SETTINGS
2 CALCULATION OF SETTINGS
2
1.
If the reach of the Zone 2 ground distance functions (Z2GRDREACH) at the remote end of the line is
less than twice the positive-sequence impedance of the line, then the proposed setting is:
Z4GRDREACH = 0.85 x Z2GRDREACH
R
2.
If the reach of the Zone 2 ground distance functions at the remote end is greater than twice the posi-
tive-sequence impedance of the line, then the proposed settings are:
Z4GRDREACH = 1.7 x Z2GRDREACH
R
–
Z
1
L
where Z2GRDREACH
R
= reach of phase Zone 2 functions at remote line terminal
Z
1
L
= positive sequence impedance of protected line
With these proposed settings, proper coordination will be obtained between the tripping and blocking func-
tions at the remote terminal of the line. It may be possible to use a shorter setting or a longer setting than
proposed, but
1.
If a longer settings is used, then the reach should be checked per the maximum allowable reach pro-
cedure given under Section 2.3.2: ZONE 2, 3, AND 4 DISTANCE FUNCTIONS on page 2–13.
2.
If a shorter reach setting is used, then the reach should be checked to assure that the function will
operate for all faults that the remote Zone 2 function can operate for.
When series capacitors are used on the protected line or in lines adjacent to the protected line, set the
Zone 4 ground distance functions with a reach that is equal to or greater than the reach of the ground dis-
tance pilot tripping functions (normally Zone 2) at the remote end of the transmission line. For example:
Z4GRDREACH
≥
Z2GRDREACH
R
where
Z2GRDREACH
R
is the reach of the ground distance pilot tripping functions (Zone 2 in this example)
at the remote end of the line.
•
Step Distance and POTT1 Schemes
In all other schemes, the Zone 4 ground distance functions can provide an additional zone of time-delayed
backup protection. They can be used to provide a fourth zone of protection in a straight Step Distance
scheme, or they can be reversed in direction to provide the so-called “reversed third” of protection.
The Zone 4 ground distance functions should be set with a reach commensurate with the application, con-
sidering underreach caused by intermediate fault current sources. Z4GRDREACH should never be set so
large as to:
1.
Exceed the maximum allowable reach (
MR
), or
2.
Cause loss of selectivity with any ground distance functions providing time-delayed backup on any
adjoining line section. If this requirement cannot be met by limiting the reach, then it may be necessary
to get this selectivity by setting timer Z4G_TIME with additional time delay.
407: Z4GCHARANG - Zone 4 Ground Characteristic Angle
•
Blocking and Hybrid Schemes
Set the Zone 4 characteristic angle to 10° less than the characteristic angle setting (Z2GCHARANG
R
) of
the Zone 2 functions at the remote terminal of the line; that is:
Z4CHARANG = Z2CHARANG
R
– 10°
•
Step Distance, POTT1, and POTT2 Schemes:
This setting determines the characteristic shape and, consequently, the area of resistance coverage pro-
vided by the Zone 4 phase distance functions. Z4PCHARANG can be set to 80° to 120° in 5° steps. A 90°
setting is recommended and lower than 90° should not be used except in blocking, hybrid and POTT2
types of schemes. If the desired reach, Z4GRDREACH, with a 90° characteristic and with maximum load
Summary of Contents for LPS-D
Page 2: ......
Page 4: ......
Page 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Page 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Page 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Page 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Page 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Page 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...