8 LOCAL USER INTERFACE
8.1 INTRODUCTION
8
Other activities using the [SET], [ACT] or [INF] keys may be performed during the relay test. When the relay
test category is re-selected, the test started earlier will be remembered only if the [END] key has not been
used. If the digital outputs were enabled, the relay will again ask if they should be disabled. If protection was
disabled, the relay will prompt to enable it before proceeding with the tests again.
NOTE: The Disable Output? screen may appear first.
To remove the relay from test mode, the select 1. End Test Mode and press the [ENT] key. The cursor can be
moved to the item in two ways: by using the arrow keys or by entering [1] followed by [ENT] key. If 1. End Test
Mode is selected, the message ON will be removed from the display line of the item under test and the relay
test terminated.
If outputs have been disabled before the relay test, a prompt appears after the selection of 1. End Test Mode
option, as shown below:
If YES is chosen, the outputs are enabled, the status LED may turn GREEN (if disabling outputs or relay test
was the cause to turn it RED), and the ACT command menu is displayed. If NO is chosen, the outputs remain
disabled, the status LED stays RED and the ACT command menu is displayed. If any other key is pressed, an
error message is generated and [CLR] key must be pressed to clear the message.
The available tests and their corresponding numbers are:
RELAY TEST
Enable outputs?
1: End Test Mode
17: ANY Z4 GND
33: ANY Z4 PHASE
2: ZONE 1 AG
18: ZONE 1 AB
34: IT DETECTOR
3: ZONE 1 BG
19: ZONE 1 BC
35: IB DETECTOR
4: ZONE 1 CG
20: ZONE 1 CA
36: GRD DIR TRIP
5: ZONE 2 AG
21: ZONE 2 AB
37: GRD DIR BLOCK
6: ZONE 2 BG
22: ZONE 2 BC
38: FAULT DETECTOR
7: ZONE 2 CG
23: ZONE 2 CA
39: REM OP DETCT
8: ZONE 3 AG
24: ZONE 3 AB
40: OUT OF STEP BLK
9: ZONE 3 BG
25: ZONE 3 BC
41: V1 DETECTOR
10: ZONE 3 CG
26: ZONE 3 CA
42: LINE OVERLOAD
11: ZONE 4 AG
27: ZONE 4 AB
43: INST PHS OVRC
12: ZONE 4 BG
28: ZONE 4 BC
44: INST GND OVRC
13: ZONE 4 CG
29: ZONE 4 CA
45: LINE PICKUP
14: ANY Z1 GND
30: ANY Z1 PHASE
46: OVER VOLTAGE
15: ANY Z2 GND
31: ANY Z2 PHASE
47: UNDER VOLTAGE
16: ANY Z3 GND
32: ANY Z3 PHASE
48:OUT OF STEP TRIP
Summary of Contents for LPS-D
Page 2: ......
Page 4: ......
Page 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Page 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Page 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Page 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Page 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Page 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...