2-
44
LPS-D Line Protection System
GE Power Management
2.3 PROTECTION SETTINGS
2 CALCULATION OF SETTINGS
2
1805: 1PDELAY2 - Single Pole Second Reclose Delay
1PDELAY2 establishes the delay to be used for the second reclose attempt following the initial single-pole trip
(this will be a three-pole reclose). The delay time can be set over a range of 0.1 to 300.0 seconds. Select a set-
ting suitable for the application.
1806: 1PDELAY3 - Single Pole Third Reclose Delay
1PDELAY3 establishes the delay to be used for the third reclose attempt following the initial single-pole trip
(this will be a three-pole reclose). The delay time can be set over a range of 0.1 to 300.0 seconds. Select a set-
ting suitable for the application.
1807: 1PDELAY4 - Single Pole Fourth Reclose Delay
1PDELAY4 establishes the delay to be used for the fourth reclose attempt following the initial single-pole trip
(this will be a three-pole reclose). The delay time can be set over a range of 0.1 to 300.0 seconds. Select a set-
ting suitable for the application.
1808: NUM3P - Number Of Attempts Following a Three-pole Trip
NUM3P establishes the number of reclosures to be attempted following a three-pole trip. NUM3P can be set to
the following:
1.
one reclosing attempt (three-pole)
2.
two reclosing attempts (all three-pole)
3.
three reclosing attempts (all three-pole)
4.
four reclosing attempts (all three-pole)
Select a setting suitable for the application.
1809: 3PDELAY1 - Three Pole First Reclose Delay
3PDELAY1 establishes the delay to be used for the first three-pole reclose attempt. The delay time can be set
over a range of 0.1 to 300.0 seconds. Select a setting suitable for the application.
1810: 3PDELAY2 - Three Pole Second Reclose Delay
3PDELAY2 establishes the delay to be used for the second three-pole reclose attempt. The delay time can be
set over a range of 0.1 to 300.0 seconds. Select a setting suitable for the application.
1811: 3PDELAY3 - Three Pole Third Reclose Delay
3PDELAY3 establishes the delay to be used for the third three-pole reclose attempt. The delay time can be set
over a range of 0.1 to 300.0 seconds. Select a setting suitable for the application.
1812: 3PDELAY4 - Three Pole Fourth Reclose Delay
3PDELAY4 establishes the delay to be used for the fourth three-pole reclose attempt. The delay time can be
set over a range of 0.1 to 300.0 seconds. Select a setting suitable for the application.
1813: RESETTIME - Reset Time
RESETTIME is the time after the reclose signal has been produced that the recloser waits before going to the
reset position. If a trip occurs during RESETTIME, the recloser goes to the next programmed reclose, or to
lockout, if the trip occurred following the last programmed reclose attempt. The reset time delay can be set
over a range of 0.1 to 300.0 seconds.
Summary of Contents for LPS-D
Page 2: ......
Page 4: ......
Page 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Page 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Page 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Page 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Page 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Page 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...