GE Power Management
LPS-D Line Protection System
1-
11
1 PRODUCT DESCRIPTION
1.3 CUSTOM PROGRAMMABILITY
1
1.3.3 CONFIGURABLE OUTPUTS
All of the LPS-D output relays, except for the alarm output relays, are user-configurable. However, each LPS-D
is shipped with default output relay assignments as shown in the Table below and Figure 1–22: ELEMENTARY
DIAGRAM WITH DEFAULT I/O ASSIGNMENTS on page 1–47.
Table 1–4: LPS-D DEFAULT OUTPUT CONTACT ASSIGNMENTS (Sheet 1 of 2)
RELAY
DESCRIPTION
MNEMONIC
INDEX #
LPS-D WITH SINGLE PHASE TRIPPING MODELS
T1
PHASE A TRIP CIRCUIT #1
TRIPA
33
T2
PHASE B TRIP CIRCUIT #1
TRIPB
34
T3
PHASE C TRIP CIRCUIT #1
TRIPC
35
T4
PHASE A TRIP CIRCUIT #2
TRIPA
33
T5
PHASE B TRIP CIRCUIT #2
TRIPB
34
T6
PHASE C TRIP CIRCUIT #3
TRIPC
35
A1
PHASE A BREAKER FAILURE INITIATE #1
TRIPA
33
A2
PHASE A BREAKER FAILURE INITIATE #2
TRIPA
33
A3
PHASE B BREAKER FAILURE INITIATE #1
TRIPB
34
A4
PHASE B BREAKER FAILURE INITIATE #2
TRIPB
34
A5
PHASE C BREAKER FAILURE INITIATE #1
TRIPC
35
A6
PHASE C BREAKER FAILURE INITIATE #2
TRIPC
35
A7
SINGLE POLE RECLOSE INITIATE #1
RI_1P
36
A8
SINGLE POLE RECLOSE INITIATE #2
RI_1P
36
A9
THREE POLE RECLOSE INITIATE #1
RI_3P
37
A10
THREE POLE RECLOSE INITIATE #2
RI_3P
37
A11
BLOCK RECLOSING
BLK-RI
144
A12
INHIBIT RECLOSING
INH-RI
145
KT1
KEY TRANSMITTER 1 / CARRIER START #1
KEY1
39
KT2
KEY TRANSMITTER 2 / CARRIER STOP #1
KEY2
40
KT3
KEY TRANSMITTER 1 / CARRIER START #1
KEY1
39
KT4
KEY TRANSMITTER 2 / CARRIER START #2
KEY2
40
C1
NON-CRITICAL ALARM
NCALM
52
C2
PT FUSE FAILURE ALARM
FF
115
Summary of Contents for LPS-D
Page 2: ......
Page 4: ......
Page 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Page 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Page 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Page 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Page 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Page 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...