
GE Power Management
LPS-D Line Protection System
1-
7
1 PRODUCT DESCRIPTION
1.2 INTRODUCTION
1
In the LPS-D relay, the four straight lines of the quadrilateral characteristic are developed from a combination
of the following three characteristics:
1.
The reactance characteristic (section 1). The tilt of the reactance characteristic is determined by the char-
acteristic timer setting. The range of this setting is 80° to 155° in 1° steps.
2.
The restricted directional characteristic (sections 2 and 4)
3.
The right (positive) resistive blinder (section 3)
The following definitions pertain to all the distance functions:
I
A
= phase A current at relay
I
B
= phase B current at relay
I
C
= phase C current at relay
I
0
= zero-sequence current at relay
V
A
= phase A to ground voltage at relay
V
B
= phase B to ground voltage at relay
V
C
= phase C to ground voltage at relay
X
1
= positive-sequence component of
X
X
2
= negative-sequence component of
X
X
M
= memory (pre-fault) value of
X
Z
x
1
= Zone
x
positive-sequence reach setting -
ZxR
∠
POSSEQANG
Z
x
0
= Zone
x
zero-sequence reach setting -
ZxR
∠
ZERSEQANG
Note: The magnitudes of
Zx
1
and
Zx
0
are identical - these quantities differ in phase angle only.
K
0
1 = Zone 1 zero-sequence compensation factor - Z1K0
K
0
= zero-sequence compensation factor
a) REACTANCE CHARACTERISTIC
The reactance characteristic used for the ground quadrilateral is the similar as the existing negative / zero
sequence phase angle comparator reactance characteristic. The function has been modified by the addition of
a fourth comparator input (Pol. #3). The operate and polarizing signals used in this function are:
Operate:
I
φ
′
Z
–
V
φ
Pol.# 1:
I
0
Z
1
Pol.# 2:
I
2
Z
1
Pol.# 3:
I
1
F
Z
1
where:
I
φ
′
Z
is the compensated
IZ
product
Z
1
is the positive sequence replica impedance
V
φ
is the phase to ground voltage
I
0
is the zero sequence current component
I
2
is the negative sequence current component, referenced to the proper phase.
I
1
F
is the fault component of the positive sequence current component, referenced to the proper
phase. The pre-fault load current is removed from this quantity.
All zones of ground reactance characteristics will have a characteristic timer with a pickup range of 90° to 155°
in 1° steps. The characteristic timer will be used to “tilt” the reactance characteristic (Tent) to prevent overreach
on non-homogeneous systems, as shown below in Figure 1–2: TENT CHARACTERISTIC. Note that the “tent”
Summary of Contents for LPS-D
Page 2: ......
Page 4: ......
Page 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Page 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Page 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Page 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Page 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Page 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...