12 ASCII COMMUNICATIONS
12
EVEnts
Display events
VIEW
List of events with date and time. Example:
06/30/98 16:26:29.7562 Host Logoff on MMI
06/30/98 16:24:37.5944 Host Logon OK on Port 2
06/30/98 16:10:45.6505 Recloser in RESET state
06/30/98 16:10:40.0000 Settings File 0 in Use
06/30/98 16:10:40.0000 System booted
Press ENTER to continue, B to go back a screen,
or ESC to quit
None
TRIP
Open Breaker command;
issues the command to
open breaker; breaker will
be determined by settings
NUM_BRKR and NUM_TC
CONTROL
Enter Breaker No. (1 / 2 / BOTH)
TRIP BREAKER 1, ! Are you sure? (Y/N)
Breaker open command sent
1, 2, or BOTH;
Y to trip, N to
cancel
CLOSe
Close Breaker command;
issues the command to
close breaker; breaker will
be determined by settings
NUM_BRKR and NUM_TC
CONTROL
Enter Breaker No. (1 / 2 / BOTH)
CLOSE BREAKER 1,! Are you sure? (Y/N)
Breaker close command sent
1, 2, or BOTH;
Y to trip, N to
cancel
ENOUT
Enable outputs
CONTROL
Enable Outputs, Are you sure? (Y/N)
Outputs are disabled or Outputs cannot be
disabled
Y for OK, N to
cancel;
command
DISABle
outputs
Disable outputs
CONTROL
Disable Outputs, Are you sure? (Y/N)
Outputs are disabled or Outputs cannot be
disabled
Y for OK, N to
cancel;
command
STATUs
Display status of the relay
VIEW
RELAY STATUS
Refer to the servicing section for status messages
for the LPS-D
Press ENTER to continue
None
DATAReset
Clear various data logs
maintained in the relay
SETTING
To clear FAULT REPORT and OSCILLOGRAPHY
enter F
To clear OST REPORT enter S
To clear EVENT DATA enter E
To reset target LED and clear warn, failure, and
trip messages enter L
To clear BREAKER HEALTH enter B
To quit press ESC
Enter your choice:
Enter letter,
press ENTER
DIGTest
Perform Digital Output
tests; the test energizes
the selected output until
END is chosen or another
output is tested
MASTER
Turn Protection off (Y/N):
Enter the number of the Digital Output to be tested
(1 to 18)
Enter END to end test
To see list of Digital Outputs enter H
To quit press ESC
Enter your choice: 4
Digital Output #4 is Activated
Turn Protection on? (Y/N):
Enter letter;
Enter digit form
1 to 18; enter
letter
Table 12–3: ASCII COMMAND LIST (Sheet 3 of 7)
ASCII
Command
Mnemonic
Command Description
Lowest
Level
Password
Needed
Relay Prompt
User Response
Summary of Contents for LPS-D
Page 2: ......
Page 4: ......
Page 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Page 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Page 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Page 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Page 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Page 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...