MACROMATIC 

INSTALLATION  INSTRUCTIONS 

ISO  4-CHANNEL  INTRINSICALLY  SAFE  RELAYS 

September 2018 

901-0000-328

Potentially  hazardous voltages are present.  Electrical shock can cause death or serious injury. 

Installation should be done by qualified personnel following all National, State & Local Codes. 

Presence de tensions potentiellement dangereuses.  Une decharge electrique peut causer la mort ou des blessures graves. 

L'installation devrait etre effectuee par du personnel qualifie suivant tous 

/es 

codes nationaux, provinciaux et /ocaux. 

BE SURE TO REMOVE ALL POWER SUPPLYING THIS EQUIPMENT BEFORE CONNECTING OR DISCONNECTING WIRING. 

READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE. KEEP FOR FUTURE REFERENCE. 

S'ASSURER DE SUPPRIMER TOUTE ALIMENTATION ELECTRIQUE DE CET EQU/PEMENT AVANT DE BRANCHER OU DE DEBRANCHER LES CABLAGES. 

LIRE LES INSTRUCTIONS AVANT D'INSTALLER OU D'UTILISER CET APPAREIL ET LES CONSERVER POUR REFERENCE ULTERIEURE. 

Installation & Wiring 

1. The ISO Series Intrinsically Safe relays are UL913 Listed as associated apparatus for interfacing between hazardous and safe areas. The

ISO relay must be installed in a suitable enclosure in a safe area.

2. For DIN-rail mounting, snap the relay on 35mm DIN track. For panel mounting, first remove both terminal connectors from the safe and hazardous

sides. Then, using a thumb, gently extend the two black DIN-rail clips from under the relay until they snap into place and the mounting hole on each

one is vis ble. Mount the relay to the panel using a #8 screw through the hole on each clip.

3. Connect all wires to the device per Macromatic Control Drawing ISD1A04 (on back). The safe (black) and hazardous (blue) terminal connectors

are removable for easier wiring and keyed to prevent incorrect wiring. Use #14-24 solid or stranded copper wire with a terminal tightening torque of 7 in-lbs.

If terminal connectors were removed, be sure to fully reinsert the terminal connectors into the proper color-coded receptacle on the device.

Operation 

The ISO Series relay consists of four intrinsically safe inputs and corresponding electromechanical relay outputs for each. There are also nine LEDs for 

status indication as defined below. 

Tile ISO se11es includes fou, conf1gwat1ons provnilng support to, a 1·.,cle vanety of applications  Eacll 

Configuration 

conf1gu

1

at1on ,s user-selecta/Jle using a 2-pos,t,on DIP s1·.1tcll easily access1/Jle on tile top of tile IYOcluct 

(see D1ag,am ,,glit)  Factory 

s111tcll 

settings 1·.111 /Je StancJa,tf Logic (STD! ancl I Jo  Delay (0 S) 

With input voltage applied, the V LED will be ON  (GREEN) to indicate power is applied.  When an input 

Standard Logic, 

device from the hazardous area is closed, the input LED is ON (GREEN); the corresponding output relay 

No Delay 

is energized and the output LED is ON (ORANGE). When the input device opens, the input LED will be 

OFF; the corresponding output relay will de-energize and the output LED will be OFF. 

With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied.  If an input 

device from the hazardous area is open when input voltage is applied, the input LED will be OFF, the 

Inverse Logic, 

corresponding output relay will be ON and the output LED will be ON (ORANGE). When an input device 

No Delay 

is closed, the input LED is ON (GREEN); the corresponding output relay will de-energize and the output 

LED will be OFF. When the input device opens, the input LED will be OFF; the corresponding output 

relay will energize and the output LED will be ON (ORANGE). 

With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied. When an input 

device from the hazardous area is closed, the input LED is ON (GREEN) and the corresponding output 

LED will FLASH (ORANGE) for 2 seconds. Then the corresponding output relay is energized and 

Standard Logic, 

the output LED is ON (ORANGE). When the input device opens, the input LED will be OFF and the 

2 Second Delay 

corresponding output LED will FLASH (ORANGE) for 2 seconds. Then the corresponding output relay 

will de-energize and the output LED will be OFF. If the input device changes state at any time during the 

delay, the corresponding output relay will remain in the current state, the output LED will stop FLASHING 

and the time delay will reset. 

With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied. If an input 

device from the hazardous area is open when input voltage is applied, the input LED will be OFF, the 

corresponding output relay will be OFF, and the output LED will FLASH (ORANGE). After 2 seconds, 

the corresponding output relay will energize and the output LED will be ON (ORANGE). When the input 

Inverse Logic, 

device closes, the input LED is ON (GREEN) and the corresponding output LED will FLASH (ORANGE). 

2 Second Delay 

After 2 seconds, the corresponding output relay will de-energize and the output LED will be OFF.  When 

the input device opens, the input LED will be OFF and the corresponding output LED will FLASH 

(ORANGE). After 2 seconds, the corresponding output relay will energize and the output LED will be 

ON (ORANGE)  If the input device changes state at any time during the delay, the corresponding output 

relay will remain in the current state, the output LED will stop FLASHING and the time delay will reset 

DIP Switch Settings 

DELAY:0S 

a

2S 

LOGIC: STD 

INV 

DELAY:0S 

Iii! 

2S 

LOGIC: STD 

INV 

DELAY:0S 

m

2S 

LOGIC: STD 

INV 

DELAY:0S 

Iii 

2S 

LOGIC: STD 

INV 

Troubleshooting: 

If the unit fails to operate properly, check that all connections are correct per Control Drawing ISD1A04. If the V LED flashes Red 

continuously, the device has been damaged and must be replaced.

Warranty: 

All catalog-listed ISO Series Intrinsically Safe Relays manufactured by Macromatic are warranted to be free from defects in workmanship or 

material under normal service and use for a period of five (5) years from date of manufacture. 