Operating Manual
LP 33 Series 60-80-100-120 kVA / S2
EPO (Emergency Power Off)
An external Emergency switch (
NC - Normally Closed
voltage-free contact) can be connected on
terminals
X2 / 1, 2
or connector
J2 / 12, 25
of the
Customer Interface
(see
Fig. 10.2.1-1 / X2 & J2
).
7
8
9
10
11
22
21
20
19
18
7
J2
X1
2
1
JP3
X2
Fig. 10.2.1-2 PCB Customer Interface
LPS33_060-080_
X7+JP
5_01
OFF
ON
OFF
ON
1
2
X7
P1 - Control board
JP5
Fig. 10.2.1-3 PCB P1 – Control board
NOTE !
To enable this function, remove jumper
JP3
on the
Customer Interface
and the cable
on the terminal
X2 / 1, 2 (
see
Fig. 10.2.1-2).
Verify if the cable on the terminal
X7 / 1, 2
and jumper
JP5
on the
P1 – Control board
are OFF
(
see
Fig. 10.2.1-3).
In a Parallel System a separate NC
(Normally Closed)
contact must be connected
individually to each unit.
When activated, this switch causes the immediate shutdown of
booster
,
battery-charger
,
inverter
; and
the
contactors K4, K6
and
K7
.
NOTE !
This procedure could imply a load shutdown.
When the
EPO
has been activated, the system must be restored as follows:
•
Press the push-button
EPO
(contact on
X7 / 1, 2
is closed again).
•
Press the key
“
O
”
(Inverter OFF
– see
Section 6.2
) on the
control panel
.
•
Press the key
“
I
”
(Inverter ON
– see
Section 6.2
) on the
control panel
.
In case of a Parallel System press the key “O” (Inverter OFF) on the control panel of
each unit connected on the parallel bus and having its output switch Q1 closed.