Modifications reserved
Page 56/103
OPM_LPS_33E_60K_M12_2GB_V010.doc
Operating Manual
LP 33 Series 60-80-100-120 kVA / S2
`
Home\Meter
MAINS
f 50
Hz
L1 230
V
L2 229
V
L3 231
V
BYPASS FREE
Bypass mains data screen
f
The frequency of the mains.
L1
L2
3-phase mains voltage PHASE /NEUTRAL.
L3
Bypass
Bypass status: FREE / LOCKED.
`
Home\Meter
INVERTER
f 50
Hz
L1 230
V
L2 230
V
L3 230
V
T OK
SYNCHRONIZED
Inverter data screen
f
The output frequency of the
Inverter
.
L1
L2
3-phase output voltage PHASE/NEUTRAL.
L3
T
The temperature of the inverter bridge (OK / MAX).
The synchronization status of the inverter with respect to
mains (Synchronized / Not Synchronized).
`
Home\Meter
MODULE LOAD
L1 :
230 V
72.0 A
50 %
L2 :
230 V
58.0 A
40 %
L3 :
230 V
43.0 A
30 %
LOAD ON INVERTER
Module load screen
… V
Output voltage PHASE/NEUTRAL for each phase.
… A
The output current as RMS values (RPA: value for
each UPS).
… %
The output load as percentage (RPA: value for
each UPS).
The source of the power supplied to the load.
`
Home\Meter
COUNTERS
Bypass mains failure
:
53
Rectifier mains failure
:
35
Overloads :
15
InvOperTime [h]
:
2135
UPSOperTime [h]
:
3125
Statistics screen
The total number of minor mains faults (bypass mains out
of tolerance faults).
The total number of times a gap of mains in the rectifier has
been reordered.
The total number of detected output overloads.
The total operating time for the
Inverter
(in hours).
The total operating time for the UPS (in hours).
`
Home\Meter
MAINS
NUMBER OF FAST TRANSIENTS
<2ms >2ms
>5ms
>10ms
25
20
7
5
ECO MODE RATE
=
70 %
ECO Mode statistic screen
This screen is enabled only for a single UPS, not for an
RPA
Parallel System
.
The number of fast transients occurred on the bypass
utility on the last seven days.
The statistic evaluation in % (100= good; 0= bad) of the
utility, for the
ECO
mode operation.