Operating Manual
LP 33 Series 60-80-100-120 kVA / S2
5.8.6
LP 33 Series 100 - 120 kVA
- Power connection with separate input mains (option)
NOTE !
Neutral of
rectifier
input and neutral of
bypass
input must be coming from the
same input bar. Inside the UPS, neutrals
N1
and
N
are connected together
.
LPS33_1
00-120_S
2_Conne
ction sep
arate_EM
C_01
X4
Battery
L1-1
-
0
+
X1
Mains 1
X2
Mains 2
X3
Load
L2-1
L3-1
N1
L1-2
L2
-2
L3
-2
N
L1
L2
L3
N2
PE
PE
PE
Fig. 5.8.6-1 Terminals for separated input mains
X1 Mains 1
Rectifier input mains connection
L1-1
= Rectifier Phase L1
L2-1
= Rectifier Phase L2
L3-1
= Rectifier Phase L3
N1
= Neutral of Rectifier Mains
PE
=
Main
Ground
X2 Mains 2
Bypass input mains connection
L1-2
= Bypass Phase L1
L2-2
= Bypass Phase L2
L3-2
= Bypass Phase L3
N
= Neutral of Bypass Mains
X3 Load
Load output connection
L1
=
Load
Phase
L1
L2
=
Load
Phase
L2
L3
=
Load
Phase
L3
N2
= Load
Neutral
PE
= Main
Ground
NOTE !
Max. rating
X1 –X2 - X3 -X4
terminals
:
150mm
2
.
Input/output terminals must be tightened with a
proper screwdriver applying torsion force 10 Nm.
Main ground (PE) cables must be connected to bus-
bar with M8 bolts. Torque wrench at 22Nm.
LPS33_040-120_Connection battery_01
+
0
-
+
0
-
X4
PE
Fig. 5.8.6-2 External battery connection
X4 Battery
External battery connection
-
= Negative pole of the battery
0
= Central point of battery blocks
+
= Positive pole of the battery
PE
= Battery cabinet ground
WARNING !
Before closing the
“external battery fuses”
, verify for correct polarity of the battery
connection
.
NOTE !
To meet standards concerning electromagnetic compliance, the connection
between the UPS and external
Battery
must be done by using a shielded cable or
suitable shielded (metal) conduit!
This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.
If the UPS is equipped with an input transformer, the secondary of the
transformer must be wye-configured with neutral solidly grounded.