Modifications reserved
Page 41/103
OPM_LPS_33E_60K_M12_2GB_V010.doc
Operating Manual
LP 33 Series 60-80-100-120 kVA / S2
5.8.3
LP 33 Series 100 - 120 kVA
- Power connection with common input mains
LPS33_1
00-120_S
2_Connec
tion comm
on_EMC_
01
X4
Battery
L1-
1
-
0
+
X1
Mains 1
X3
Load
L2
-1
L3
-1
N1
L1
L2
L3
N2
PE
PE
PE
Fig. 5.8.3-1 Terminals for common input mains
X1 Mains 1 - Mains input connection
L1-1
= Rec Bypass Phase L1
L2-1
= Rec Bypass Phase L2
L3-1
= Rec Bypass Phase L3
N
=
Mains
Neutral
PE
=
Main
ground
X3 Load - Load output connection
L1
= Load
Phase
L1
L2
= Load
Phase
L2
L3
= Load
Phase
L3
N
=
Load
Neutral
PE
= Load
Ground
NOTE !
Max. rating
X1 – X3 - X4
terminals
:
150mm
2
.
Input/output terminals must be tightened with a proper screwdriver applying
torsion force 10 Nm.
Main ground (PE) cables must be connected to bus bar with M8 bolts.
Torque wrench at 22Nm.
LPS33_040-120_Connection battery_01
+
0
-
+
0
-
X4
PE
Fig. 5.8.3-2 External battery connection
X4 Battery - External battery connection
-
= Negative pole of the battery
0
= Central point of battery blocks
+
= Positive pole of the battery
PE
= Battery cabinet ground
WARNING !
Before closing the
“external battery fuses”
, verify for correct polarity of the battery
connection
.
NOTE !
To meet standards concerning electromagnetic compliance, the connection
between the UPS and external
Battery
must be done by using a shielded cable or
suitable shielded (metal) conduit!
This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.
If the UPS is equipped with an input transformer, the secondary of the
transformer must be wye-configured with neutral solidly grounded.