Operating Manual
LP 33 Series 60-80-100-120 kVA / S2
`
Home\Setup\User
MODEM
Tel 2
:
2
Tel 2 enabled
:
N
Tel 3
:
3
Tel 3 enabled
:
N
Tel 4
:
4
Tel 4 enabled
:
N
V
Modem screen 2
Tel 2
It records the
second dial-out number
.
Tel 2
enabled
This parameter
Y/N
specifies if the
second telephone number
will be used for dial-out.
Tel 3
It records the
third dial-out number
.
Tel 3 enabled
This parameter
Y/N
specifies if the
third
telephone number
will be used for dial-out.
Tel 4
It records the
fourth dial-out number
.
Tel 4 enabled
This parameter
Y/N
specifies if the
fourth telephone number
will be used for dial-out.
`
Home\Setup\User
DISPLAY
UPS name
:
LP Series
Language :
ENGLISH
Contrast
V
LCD Display screen
UPS Name
The user can choose the name of the UPS
model shown on the main page (max. 9
characters).
Language
This parameter allows the choice of
language used to display the information.
Valid choices are:
English, German, Italian, Spanish, French,
Finnish, Polish, Portuguese, Czech, Slovakian, Chinese,
Swedish, Russian and Dutch
.
Contrast
This parameter controls the contrast of the
LCD screen in ten steps (0 – 9).
`
Home\Setup\User
ECO MODE
Enabled :
N
DAY OF WEEK
d1 d2
d3
d4
d5
d6
d7
HOURS / DAY
24 24 12 12 12 12 12
ECO MODE screen
This screen is enabled only for a single UPS, not for an
RPA
Parallel System
.
Enabled
This parameter (values
Y
/
N
) enables or disables the
operation in
ECO Mode
.
If the value is
Y
and the current time is in the interval for the
current day, the
ECO Mode
is active.
The activation / deactivation of
ECO Mode
is indicated each
time in the event list.
In order to check the
inverter
function, at least
1 minute
of
VFI
mode must be programmed during the week (the
Y/N
parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in
VFI mode
is not respected, the
ECO Mode
will be disabled.
If the value is
N
, the UPS is normally operating in
VFI / double conversion mode
at all times.
DAY OF WEEK (d1 ÷ d7): Enabling time in function of weekdays
For the weekdays from
d1
to
d7
(Saturday to Friday)
the edit mode (edit day) allows to define time intervals when
the UPS is operating in
ECO Mode
. The hour is given in 24-hour format.
These intervals are defined by:
ECO Mode START
:
The hour of the day after which the
ECO Mode
is enabled.
The
ECO Mode
is enabled until the following
ECO Mode STOP
time is reached (the
ECO Mode
STOP
time of the same day if this is later than the
ECO Mode START
time, the
ECO Mode
STOP
time of the following day otherwise).
ECO Mode STOP
:
The hour of the day before which the
ECO Mode
is enabled.
The
ECO Mode
is enabled starting from the preceding
ECO Mode START
time (the
ECO Mode START
time of the
same day if this is earlier than the
ECO Mode STOP
time, the
ECO Mode START
time of the previous day otherwise).
Identical times for
ECO Mode START
and
ECO Mode STOP
maintain the existing mode only in case the previous
command was
ECO Mode START
and the following command will be
ECO Mode STOP
.
HOURS / DAY
:
The number of
ECO Mode
hours per weekday (from
d1
- Saturday
to
d7
- Friday
) is displayed in the operation
mode parameter window (ceiling value).